Section 15096
PIPE HANGERS AND SUPPORTS
PART 1 - GENERAL
1.1 THE REQUIREMENT
A. This Section specifies
hangers and supports for all piping systems specified in Section
15050. This Section does not
include pipe supports for fire sprinkler systems, pipe
anchors, guides or seismic restraints.
B. The hangers and supports specified
in this Section are provided to resist pipe loads occurring primarily
in the downward (gravity) direction. For the purpose of pipe hanger
and support selection, this Section establishes pipe support
classifications based on the operating temperatures of the piping
contents. Pipe support classifications are as follows:
1. Hot Systems
A - 1. 120 degrees F to 450 degrees F A
- 2. 451 degrees F to 750 degrees F A - 3. Over 750 degrees F
2. Ambient Systems
B - 60 degrees F to 119 degrees F
3. Cold Systems
C - 1. 33 degrees F to 59 degrees F C -
2. -20 degrees F to 32 degrees F
C. Hanger and Support Selection
1. The Contractor shall select pipe
hangers and supports as specified in the Contract
Documents. Selections shall be based upon the pipe support
classifications specified in this Section, the piping insulation
thickness specified, and any special requirements that may be
specified in the Contract Documents.
2. The Contractor shall review the
piping layout in relation to the surrounding structure and adjacent
piping and equipment before selecting the type of support to be used
at each hanger point.
3. Hangers and supports shall withstand
all static and specified dynamic conditions of loading to which the
piping and associated equipment may be subjected. As a minimum,
consideration shall be given to the following conditions:
a. Weights of pipe, valves, fittings,
insulating materials, suspended hanger components, and normal fluid
contents.
b. Weight of
hydrostatic test fluid or cleaning fluid if normal operating fluid
contents are lighter.
c. Reaction forces due to the
operation of safety or relief valves. d. Wind, snow or ice
loadings on outdoor piping.
4. Hangers and supports shall be sized
to fit the outside diameter of pipe, tubing, or, where specified, the
outside diameter of insulation.
5. Where negligible movement occurs at
hanger locations, rod hangers shall be used for suspended lines,
wherever practical. For piping supported from below, bases, brackets
or structural cross members shall be used.
6. Hangers for the suspension of size 2
1/2 inches and larger pipe and tubing shall be capable of vertical
hanger component adjustment under load.
7. The supporting systems shall
provide for and control the free or intended movement of the
piping including its movement in relation to that of connected
equipment.
8. Where there is horizontal movement
at a suspended type hanger location, hanger components shall be
selected to allow for swing. The vertical angle of the hanger rod
shall not, at any time, exceed 4 degrees.
9. There shall be no contact between a
pipe and hanger or support component of dissimilar metals. Prevent
contact between dissimilar metals when supporting copper tubing by
use of copper-plated, rubber, plastic or vinyl coated, or stainless
steel hanger and support components.
10. Unless otherwise specified,
existing pipes and supports shall not be used to support new
piping.
11. Unless otherwise specified, pipe
support components shall not be attached to pressure vessels.
12. Stock hanger and support
components shall be used wherever practical.
1.2 REFERENCES
A. This Section contains references to
the following documents. They are a part of this Section as
specified and modified. In case of a conflict between the
requirements of this Section and those of the listed documents, the
requirements of this Section shall prevail.
AISC Manual of Steel American
Institute of Steel Construction, Construction Manual of
Steel Construction, Allowable Stress Design - 9th Edition
MSS SP-58-88 Pipe
Hangers and Supports - Materials, Design and
Manufacture
MSS SP-69-83 Pipe
Hangers and Supports - Selection and Application
FEDSPEC
Hangers and Supports, Pipe
WW-H-171e-78
MFMA-1-84
Metal Framing Standards Publication
PART 2 -
PRODUCTS
2.1 ACCEPTABLE PRODUCTS
A. Standard pipe supports and
components shall be manufactured by B-Line, Carpenter &
Patterson, Kin-Line, Anvil, Michigan, Pipe Shields Incorporated,
Superstrut, Unistrut, or equal. Pipe support components shall
conform to the requirements of MSS SP-69 and FEDSPEC WW-H-171e. Pipe
support materials shall conform to the requirements of MSS
SP-58. Metal framing system components shall conform to the
metal framing manufacturers' Association Standard MFMA-1.
2.2 MATERIALS
A. Unless otherwise specified, pipe
hangers and supports, structural attachments, fittings and
accessories shall be hot-dip or mechanically galvanized after
fabrication. Nuts, bolts and washers may be zinc-plated except for
those subject to moisture or corrosive atmosphere, which shall be
type 304 stainless steel.
B. Pipe Hangers and Supports
1. Type 1 – Clevis Pipe Hanger:
Clevis hangers shall be carbon steel with configuration and
components equivalent to MSS and FEDSPEC Type 1.
a. Steel pipe (insulated) shall be
B-Line B3100, Anvil Fig. 260, or equal, with insulation shield.
b. Steel pipe (uninsulated)
shall be B-Line B3100, Anvil Fig. 260, or equal.
c. Cast and ductile iron pipe
shall be B-Line B3102, Anvil Fig. 590, or equal.
d. Copper pipe (uninsulated) shall be
B-Line B3104 CT, Anvil Fig. CT-65, or equal.
e. Copper pipe (insulated) shall be
B-Line B3100, Anvil Fig. 260, or equal, with insulation shield.
f. Plastic pipe shall be B-Line B3100
C, Carpenter & Patterson Fig. 100PVC, or equal.
2. Type 2 - "J" Pipe Hanger:
Hangers shall be carbon steel with configuration and components
equivalent to MSS Type 5. This hanger shall be used only on
uninsulated pipe.
a. Steel pipe shall be B-Line B3690,
Anvil Fig. 67, Michigan model 418, or equal.
b. Copper and plastic pipe
shall be Michigan model 419, Unistrut J 1205N
series, or equal.
3. Type 3 – Double Bolt Pipe
Clamp: Pipe clamp shall be carbon steel, with configuration
and components equivalent to MSS and FEDSPEC Type 3.
a. Steel pipe (insulated) shall be
B-Line B3144, Anvil Fig. 295, or equal, with insulation shield.
Insulation shield is optional for hot and ambient systems.
b. Steel pipe (uninsulated)
shall be B-Line B3144, Anvil Fig. 295, or equal.
c. Copper
pipe (insulated only) shall be B-Line B3144, Anvil Fig. 295, or
equal, with insulation shield.
4. Type 4 – Adjustable Roller Hanger:
Rollers shall be cast iron, yoke and cross bolt shall be carbon
steel. Configuration and components shall be equivalent to MSS Type
43 and FEDSPEC Type 44.
a. Steel pipe (insulated) shall be
B-Line B3110, Anvil Fig. 181, or equal, with insulation shield.
b. Steel pipe (uninsulated)
shall be B-Line B3110, Anvil Fig. 181, or equal.
c. Copper pipe (insulated only) shall
be B-Line B3110, Anvil Fig. 181, or equal, with insulation shield.
d. Plastic pipe shall be
B-Line B3110, Anvil Fig. 181, or equal.
5. Type 5 – Single Pipe Roll:
Rollers and sockets shall be cast iron, cross rod shall be steel.
Configuration and components shall be equivalent to MSS Type 41 and
FEDSPEC Type 42.
a. Steel pipe (insulated) shall be
B-Line B3114, Anvil Fig. 171, or equal, with insulation shield.
b. Steel pipe (uninsulated)
shall be B-Line B3114, Anvil Fig. 171, or equal. c. Plastic
pipe shall be B-Line B3114, Anvil Fig. 171, or equal.
6. Type 6 – Framing Channel Pipe
Clamp: Pipe clamps shall be steel with galvanized finish and material
thickness as listed below:
a. Steel pipe (uninsulated):
Pipe size 3/8 inch and 1/2 inch shall be 16 gage;
3/4 inch through 1 1/4 inches shall
be 14 gage; 1 1/2 inches through
3 inches shall be 12 gage; 3 1/2 inches
through 5 inches shall be 11 gage;
6 and 8 inches shall be 10 gage;
Michigan model 431, Powerstrut PS
1100, Unistrut P 1109 series, or equal.
b. Steel pipe (insulated):
Pipe clamp shall be as described in Paragraph
15096-2.2 B.6.a with insulation shield.
c. Copper (uninsulated) and plastic
pipe: Pipe size 3/8 inch and 1 inch shall be 16 gage; 1-1/4 inches
and 1-1/2 inches shall be 14 gage; 2 inches through 3 inches shall be
12 gage; 4 inches shall be 11 gage; clamp shall be copper-plated,
plastic coated or lined with dielectric material; Michigan model 432,
Powerstrut PS 1200, Unistrut P 2024C and P 2024PC series, or equal.
d. Copper pipe (insulated):
Pipe clamp shall be as described in Paragraph
15096-2.2 B.6.a with insulation shield.
7. Type 7 - U-Bolt: U-bolts
shall be carbon steel with configuration equivalent to MSS
and FEDSPEC Type 24.
a. Steel pipe (uninsulated)
shall be Anvil Fig. 137, B-Line B3188, or equal.
b. Steel pipe (insulated) shall be
Anvil Fig. 137, B-Line B3188, or equal, with insulation shield.
c.
Cast and ductile iron pipe shall be Anvil Fig. 137, B-Line B3188, or
equal.
d. Copper pipe (uninsulated) shall be
Carpenter & Patterson Fig. 222 CT, B- Line B3501 CT, Anvil Fig.
137C, or equal.
e. Copper pipe (insulated) shall be
Anvil Fig. 137, B-Line B3188, or equal, with insulation shield.
f. Plastic pipe shall be
Anvil Fig. 137C, Michigan model 151, B-Line B3188
C, or equal.
8. Type 8 – Adjustable Pipe Roll
Support: Rollers and sockets shall be cast iron, cross rod and
support rods shall be carbon steel.
a. Steel pipe (insulated) shall be
B-Line B3122, Anvil Fig. 177, or equal, with insulation shield.
b. Steel pipe (uninsulated)
shall be B-Line B3122, Anvil Fig. 177, or equal.
c. Copper pipe (insulated only) shall
be B-Line B3122, Anvil Fig. 177, or equal, with insulation shield.
d. Plastic pipe shall be
B-Line B3122, Anvil Fig. 177, or equal.
9. Type 9 – Welded Pipe Stanchion:
Minimum material thickness shall be standard schedule carbon steel
pipe, cut to match contour of the pipe elbow. Use of this support
shall be limited to ambient systems only.
10. Type 10 – Pipe Stanchion Saddle:
Saddles and yokes shall be carbon steel and comply with MSS Type 37
and FEDSPEC Type 38.
a. Steel pipe (insulated)
shall be Carpenter & Patterson Fig. 125, B-Line
B3090, or equal, with insulation
shield.
b. Steel pipe (uninsulated)
shall be Carpenter & Patterson Fig. 125, B-Line
B3090, or equal.
c. Cast and ductile iron pipe
shall be Carpenter & Patterson Fig. 125, B-Line
B3090 NS, or equal.
d. Copper pipe (uninsulated)
shall be Carpenter & Patterson Fig. 125, B-Line
B3090, or equal, with insulation shield
or lined with dielectric material.
e. Copper pipe (insulated)
shall be Carpenter & Patterson Fig. 125, B-Line
B3090, or equal, with insulation
shield.
f. Plastic pipe shall be Carpenter &
Patterson Fig. 125, B-Line B3090, or equal.
11. Type 11 – Offset Pipe Clamp:
Pipe clamp shall be carbon steel with configuration and components as
specified and shall be of standard design manufactured by a pipe
hanger component manufacturer.
a. Steel pipe (insulated) shall be
B-Line B3148, Anvil Fig. 103, or equal, with insulation shield.
b. Steel pipe (uninsulated)
shall be B-Line B3148, Anvil Fig. 103, or equal.
c. Cast and
ductile iron pipe shall be B-Line B3148 NS, Anvil Fig. 103, or equal.
d. Copper pipe (insulated) - shall be
B-Line B3148, Anvil Fig. 103, or equal, with insulation shield.
e. Copper pipe (uninsulated) shall be
B-Line B3148, Anvil Fig. 103, or equal, lined with dielectric
material.
f. Plastic pipe shall be
B-Line B3148, Anvil Fig. 103, or equal.
g. Vertical pipe support applications
shall be as specified above except that insulation shields shall not
be used for insulated pipe.
12. Type 12 - Riser Clamp: Riser clamp
shall be carbon steel with configuration and components equivalent to
MSS and FEDSPEC Type 8.
a. Steel pipe (insulated)
shall be B-Line B3373, Anvil Fig. 261, or equal.
b. Steel pipe (uninsulated)
shall be B-Line B3373, Anvil Fig. 261, or equal.
c. Cast and ductile iron pipe
shall be B-Line B3373, Anvil Fig. 261, or equal.
d. Copper pipe (insulated) shall be
B-Line B3373 CT, Anvil Fig. CT-121, Michigan model 511, or equal.
e. Copper pipe (uninsulated) shall be
B-Line B3373 CT, Anvil Fig. CT-121, Michigan model 511, or equal.
f. Plastic pipe shall be
B-Line B3373, Anvil Fig. 261c, or equal.
13. Type 13 - Framing Channel Pipe
Strap: Pipe strap shall be carbon steel, with configuration
equivalent to MSS Type 26.
a. Steel pipe (uninsulated)
shall be Superstrut No. C-708-U, Powerstrut PS
3126, Kin-Line No. 477, or equal.
b. Steel pipe (insulated)
shall be Superstrut No. C-708-U, Powerstrut PS
3126, Kin-Line No. 477, or equal, with
insulation shield.
c. Copper pipe (uninsulated)
shall be Superstrut No. C-708-U, Powerstrut PS
3126, Kin-Line No. 477, or equal,
with insulation shield or lined with dielectric material.
d. Copper pipe (insulated)
shall be Superstrut No. C-708-U, Powerstrut PS
3126, Kin-Line No. 477, or equal, with
insulation shield.
e. Plastic pipe shall be Superstrut No.
C-708-U, Powerstrut PS 3126, Kin- Line No. 477, or equal.
C. Rack and Trapeze Supports
1. General: Unless otherwise
specified, trapeze and pipe rack components shall have a minimum
steel thickness of 12 gage, with a maximum deflection 1/240 of the
span.
2. Type 20 -
Trapeze Pipe Support: Trapeze pipe support cross members shall be
framing channel as specified in Paragraph 15096-2.2 E.5. Flat plate
fittings shall be 1 5/8-inch square carbon steel of standard design
manufactured by framing channel manufacturer, Unistrut P2471, B-Line
B202-2, or equal.
3. Type 21 - Pipe Rack Support: Post
and cross members shall be framing channel as specified in Paragraph
15096-2.2 E.5. Pipe rack fittings shall be carbon steel, of standard
design manufactured by framing channel manufacturer.
90-degree fittings shall be gusseted Unistrut P2484, B-Line B844, or
equal. Post base fittings shall be as specified in Paragraph
15096-2.2 D.5.
D. Structural Attachments
1. Type A – Malleable Iron Concrete
Insert: Concrete inserts shall be malleable iron and comply with MSS
and FEDSPEC Type 18. Anvil Fig. 282, Carpenter & Patterson Fig.
108, or equal.
2. Type B - Side Beam Bracket:
Bracket shall be malleable iron and comply with
MSS Type 34 and FEDSPEC Type 35. Anvil
Fig. 202, B-Line B3062, or equal.
3. Type C - Malleable Beam Clamp with
Extension Piece: Clamp and extension piece shall be malleable iron,
tie rod shall be steel. Beam clamp shall comply with MSS and FEDSPEC
Type 30. Anvil Fig. 218 with Fig. 157 extension piece, B-Line
B3054, or equal.
4. Type D - Steel Beam Clamp with Eye
Nut: Beam clamp and eye nut shall be forged steel.
Configuration and components shall comply with MSS and FEDSPEC
Type 28. Anvil Fig. 292, Carpenter & Patterson Fig. 297, or
equal.
5. Type E - Framing Channel Post Base:
Post bases shall be carbon steel, of standard design manufactured by
framing channel manufacturer. Single channel: Unistrut P2072A,
B-Line B280, or equal. Double channel: Unistrut P2073A, B-Line B281,
or equal.
6. Type F - Welded Beam Attachment:
Beam attachment shall be carbon steel and comply with MSS and FEDSPEC
Type 22. B-Line B3083, Anvil Fig. 66, or equal.
7. Type G - Welded Steel Bracket:
Bracket shall be carbon steel and comply with MSS Type 32 and FEDSPEC
Type 33 for medium welded bracket. Heavy welded bracket shall comply
with MSS Type 33 and FEDSPEC Type 34.
8. Type H – Cast Iron
Bracket: Bracket shall be cast iron, Carpenter & Patterson Fig.
340, or equal.
9. Type J - Adjustable Beam Attachment:
Beam attachment shall be carbon steel, Carpenter & Patterson
Fig. 151, B-Line B3082, or equal.
10. Type K - Double Channel Bracket:
Wall channel shall be single channel framing channel as specified in
Paragraph 15096-2.2 E.5. Cantilever bracket shall be a carbon steel
double framing channel assembly, Unistrut P2542 through P2546, B-
Line B297-12 through B297-36, or equal.
11. Type L -
Single Channel Bracket: Wall channel shall be single channel framing
channel as specified in Paragraph 15096-2.2 E.5. Cantilever bracket
shall be a carbon steel single framing channel assembly, Unistrut
P2231 through P2234, B- Line B198-6, B198-12, B196-18 and B196-24, or
equal.
12. Type M - Wall Mounted Channel:
Wall channel shall be single channel framing channel as specified in
Paragraph 15096-2.2 E.5.
13. Type N - Pipe Stanchion
Floor Attachment: Baseplate shall be carbon steel with
1/2 inch minimum thickness. Anchor
bolt holes shall be 1/16 inch larger than the anchor bolt diameter.
The space between the baseplate and the floor shall be filled with
nonshrink grout.
E. Accessories
1. Hanger Rods: Rods shall be carbon
steel, threaded on both ends or continuous threaded and sized as
specified.
2. Weldless Eye Nut: Eye nut
shall be forged steel and shall comply with MSS and
FEDSPEC Type 17. Eye nut shall be Anvil
Fig. 290, B-Line B3200, or equal.
3. Welded Eye Rod: Eye rod shall be
carbon steel with eye welded closed. Inside diameter of eye shall
accommodate a bolt diameter 1/8 inch larger than the rod diameter.
Eye rod shall be Anvil Fig. 278, B-Line B3211, or equal.
4. Turnbuckle: Turnbuckle
shall be forged steel and shall comply with MSS and
FEDSPEC Type 13. Turnbuckle shall be
Anvil Fig. 230, B-Line B3202, or equal.
5. Framing Channel: Framing channel
shall be 1 5/8 inches square, roll formed, 12- gage carbon steel.
Channel shall have a continuous slot along one side with in- turned
clamping ridges. Single channel: Unistrut P1000, B-Line B22, or
equal. Double channel: Unistrut P1001, B-Line B22A, or equal.
Triple channel: Unistrut P1004A, B-Line B22X, or equal.
2.3 THERMAL PIPE HANGER SHIELD
Thermal shields shall be provided at
hanger, support and guide locations on pipe requiring insulation. The
shield shall consist of an insulation layer encircling the entire
circumference of the pipe and a steel jacket encircling the
insulation layer. The thermal shield shall be the same thickness as
the piping system insulation specified in Section 15250. The
standard shield shall be used for hot systems and the vapor barrier
shield shall be used for cold systems. Stainless steel band clamps
shall be used where specified to ensure against slippage between the
pipe wall and the thermal shield.
A. Standard Shield
1. Insulation
a. Hydrous calcium silicate,
high density, waterproof b. Compressive strength: 100 psi
average
c. Flexural strength: 75 psi
average
d. K
factor: 0.38 at 100 degrees F mean
e. Temperature range: 20
degrees F to 500 degrees F
2. Steel Jacket: Galvanized steel.
Gage shall be the manufacturer's standard supplied for the
given pipe size.
3. Connection: Shield shall have butt
connection to pipe insulation. Steel jacket and insulation shall be
flush with end.
B. Vapor Barrier Shield
1. Insulation
a. Hydrous calcium silicate,
high density, waterproof. b. Compressive strength: 100 psi
average.
c. Flexural strength: 75 psi
average.
d. K factor: 0.38 at 100
degrees F mean.
e. Temperature range: 20
degrees F to 500 degrees F.
2. Steel Jacket: Galvanized steel.
Gage shall be the manufacturer's standard supplied for the
given pipe size.
3. Connection: Shield shall have butt
connection to pipe insulation. Insulation shall extend 1 inch each
side of steel jacket for vapor tight connection to pipe insulation
vapor barrier.
2.4 PRODUCT DATA
A. Hanger and support locations and
components shall be indicated on the piping layout drawings required
by Paragraph 15050-2.4.
PART 3 - EXECUTION
3.1 HANGER AND SUPPORT LOCATIONS
A. The Contractor is cautioned
that the drawings generally show the type of pipe supports and
hangers required and do show all of the hangars and supports
required. The Contractor is cautioned that additional hangers and
supports will be required to properly support the piping systems in
accordance with applicable sections of the Specifications and
drawings.
B. The Contractor shall locate hangers
and supports as near as possible to concentrated loads such as
valves, flanges, etc. Locate hangers, supports and accessories
within the maximum span lengths specified in the Contract Documents
to support continuous pipeline runs unaffected by concentrated loads.
C. At least one hanger or
support shall be located within 2 feet from a pipe change in
direction. D. The Contractor shall locate hangers and
supports to ensure that connections to equipment,
tanks, etc., are substantially free
from loads transmitted by the piping.
E. Where
piping is connected to equipment, a valve, piping assembly, etc. that
will require removal for maintenance, the piping shall be supported
in such a manner that temporary supports shall not be necessary for
this procedure.
F. Pipe shall not have pockets formed
in the span due to sagging of the pipe between supports caused by the
weight of the pipe, medium in the pipe, insulation, valves and
fittings.
3.2 INSTALLATION
A. Welded and bolted attachments to the
building structural steel shall be in accordance with the
requirements of the AISC Manual of Steel Construction. Unless
otherwise specified, there shall be no drilling or burning of holes
in the building structural steel.
B. Hanger components shall not be
used for purposes other than for which they were designed.
They shall not be used for rigging and erection purposes.
C. The Contractor shall install items
to be embedded before concrete is poured. Fasten embedded items
securely to prevent movement when concrete is poured.
D. Embedded anchor bolts shall be used
instead of concrete inserts for support installations in areas below
water surface or normally subject to submerging.
E. The Contractor shall install thermal
pipe hanger shields on insulated piping at required locations during
hanger and support installation. Butt joint connections to pipe
insulation shall be made at the time of insulation installation in
accordance with the manufacturer's recommendations.
F. Hanger and support components in
contact with plastic pipe shall be free of burrs and sharp edges.
G. Rollers shall roll freely
without binding.
H. Finished floor beneath Type N
structural attachments and framing channel post bases shall be
roughed prior to grouting. Grout between base plate and floor shall
be free of voids and foreign material.
I. Baseplates shall be cut and drilled
to specified dimensions prior to welding stanchions or other
attachments and prior to setting anchor bolts.
J. Plastic or rubber end caps shall be
provided at the exposed ends of all framing channels that are located
up to 7 feet above the floor.
3.3 ADJUSTMENTS
A. The Contractor shall adjust
hangers and supports to obtain required pipe slope and
elevation. Shims made of material that is compatible with the piping
material may be used. Stanchions shall be adjusted prior to grouting
their baseplates.
END OF SECTION
No comments:
Post a Comment