Section 15112
SOLENOID VALVES
PART 1 – GENERAL
1.1 THE REQUIREMENT
A. The work of this Section includes
providing 2- and 3-way solenoid valves, direct or pilot operated
type, for control of process fluids, complete and operable.
1.2 REFERENCE SPECIFICATIONS,
CODES AND STANDARDS
A. The Work of the following sections
applies to the Work of this Section. Other sections of the
Specifications, not referenced below, shall also apply to the extent
required for proper performance of this work
1. General Conditions
2. Section 15100, Valves,
General
B. Comply with the current
provisions of the following Codes and Standards:
1. UL 429
Electrically Operated Valves
2. UL 1002
Electrically Operated Valves for Use in Hazardous Locations
1.3 QUALITY ASSURANCE
A. Valves shall be listed by
Underwriters Laboratories Inc. in accordance with UL 429 and
UL 1002. Solenoid valves for gas
service shall be approved by Factory Mutual.
PART 2 – PRODUCTS
2.1 GENERAL
A. Unless otherwise specified,
solenoid valves shall be designed to seal the pressurized
(supply) port upon deenergization.
B. The minimum acceptable
operating pressure differential for pilot operated valves shall be
5 psi.
2.2 TYPE
A. Valves with piping connections less
than 1-1/2 inches in diameter shall be direct-acting type.
B. Valves with piping connections
1-1/2 inches in diameter and greater shall be pilot operated
globe body type.
2.3
VALVE CONSTRUCTION
A. Solenoid valves shall be of the
size, type and class indicated and shall be designed for not less
than 150 psi working pressure. Valves for water or air service shall
have brass or bronze bodies with screwed ends, stainless steel trim
and spring, Teflon or other resilient seals with material best suited
for the temperature and fluid handled. Solenoid valves in indicated
corrosive environments shall have stainless steel bodies. For
chemicals and all corrosive fluids, solenoid valves with Teflon
bodies and springs or other suitable materials shall be used.
General purpose enclosures for indoors shall be NEMA Type 2. For
explosion-proof, corrosive, special purpose or outdoor locations,
NEMA Type 4, 7, 9, 9E, 9F or 9G enclosures shall be used, as
applicable. All coil ratings shall be for continuous duty. For
electrical characteristics, see electrical drawings or
specifications.
2.4 MANUFACTURERS
A. Solenoid valves shall be
manufactured by one of the following or equal:
1. For general duty
a. Direct Acting Type
(1) ASCO
(2) Honeywell-Skinner b.
Pilot Type
(1) Cla-Val Co.
(2) Golden Anderson
2. For corrosive fluids
a. Valcor Engineering
Corporation b. GF Plastic Systems, Inc.
PART 3 – EXECUTION
3.1 INSTALLATION
A. Installation shall be in
accordance with the manufacturer’s recommendations and Section
15100.
B. Solenoid valves shall be installed
in accordance with all mechanical, electrical, and instrumentation
drawings and specifications where required for the specific
operation.
END OF SECTION