SECTION 15408 PLUMBING PIPE INSULATION

This spec was part of the Des Plaines, IL River WRF project that bid Feb 26, 2015.


SECTION 15408 PLUMBING PIPE INSULATION
PART 1 - GENERAL

1.1 SUMMARY

A. This Section includes preformed, rigid and flexible pipe insulation; insulating cements; field-applied jackets; accessories and attachments; and sealing compounds.

1.2 QUALITY ASSURANCE

A. Installer Qualifications: Skilled mechanics who have successfully completed an ap- prenticeship program or another craft training program certified by the U.S. Depart- ment of Labor, Bureau of Apprenticeship and Training.

B. Fire-Test-Response Characteristics: As determined by testing materials identical to those specified in this Section according to ASTM E 84, by a testing and inspecting agency acceptable to authorities having jurisdiction. Factory label insulation and jacket materials and sealer and cement material containers with appropriate markings of ap- plicable testing and inspecting agency.

1. Insulation Installed Indoors: Flame-spread rating of 25 or less, and smoke- developed rating of 50 or less.

2. Insulation Installed Outdoors:   Flame-spread rating of 75 or less, and smoke- developed rating of 150 or less.

1.3 DELIVERY, STORAGE, AND HANDLING

A. Packaging: Ship insulation materials in containers marked by manufacturer with ap- propriate ASTM specification designation, type and grade, and maximum use tempera- ture.

1.4 COORDINATION

A. Coordinate size and location of supports, hangers, and insulation shields specified in Division 15 Section "Hangers and Supports."

B. Coordinate clearance requirements with piping Installer for insulation application.

1.5 SCHEDULING

A. Schedule insulation application after testing piping systems and, where required, after installing and testing heat-trace tape. Insulation application may begin on segments of piping that have satisfactory test results.

PART 2 - PRODUCTS

2.1 MANUFACTURERS

A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

1. Mineral-Fiber Insulation:

a. CertainTeed Manson.
b. Knauf FiberGlass GmbH.
c. Owens-Corning Fiberglas Corp.
d. Schuller International, Inc.

2.2 INSULATION MATERIALS

A. Mineral-Fiber Insulation: Glass fibers bonded with a thermosetting resin complying with the following:

1. Preformed Pipe Insulation:   Comply with ASTM C 547, Type 1, with factory- applied, all-purpose, vapor-retarder jacket.

2. Fire-Resistant Adhesive:   Comply with MIL-A-3316C in the following classes and grades:

a. Class 1, Grade A for bonding glass cloth and tape to unfaced glass-fiber in- sulation, for sealing edges of glass-fiber insulation, and for bonding lag- ging cloth to unfaced glass-fiber insulation.
b. Class 2, Grade A for bonding glass-fiber insulation to metal surfaces.

3. Vapor-Retarder Mastics:  Fire- and water-resistant, vapor-retarder mastic for in- door applications.  Comply with MIL-C-19565C, Type II.

4. Mineral-Fiber Insulating Cements:  Comply with ASTM C 195.

5. Expanded   or   Exfoliated   Vermiculite   Insulating   Cements: Comply   with ASTM C 196.

6. Mineral-Fiber, Hydraulic-Setting Insulating and Finishing Cement:  Comply with ASTM C 449/C 449M.

B. Flexible Elastomeric Thermal Insulation: Closed-cell, sponge- or expanded-rubber ma- terials. Comply with ASTM C 534, Type I for tubular materials and Type II for sheet materials.

1. Adhesive:  As recommended by insulation material manufacturer.

2. Ultraviolet-Protective Coating:  As recommended by insulation manufacturer.

C. Prefabricated Thermal Insulating Fitting Covers:   Comply with ASTM C 450 for di- mensions used in preforming insulation to cover valves, elbows, tees, and flanges.

2.3 FIELD-APPLIED JACKETS

A. General: ASTM C 921, Type 1, unless otherwise indicated.

B. Foil and Paper Jacket:  Laminated, glass-fiber-reinforced, flame-retardant kraft paper and aluminum foil.

C. PVC Jacket:  High-impact, ultraviolet-resistant PVC; 20 mils (0.5 mm) thick; roll stock ready for shop or field cutting and forming.

1. Adhesive:  As recommended by insulation material manufacturer.

2. PVC Jacket Color: White.

D. Standard PVC Fitting Covers:  Factory-fabricated fitting covers manufactured from 20- mil- (0.5-mm-) thick, high-impact, ultraviolet-resistant PVC.

1. Shapes: 45- and 90-degree, short- and long-radius elbows, tees, valves, flanges, reducers, end caps, soil-pipe hubs, traps, mechanical joints, and P-trap and supply covers for lavatories for the disabled.

2. Adhesive:  As recommended by insulation material manufacturer.

2.4 ACCESSORIES AND ATTACHMENTS

A. Bands:  3/4 inch (19 mm) wide, in one of the following materials compatible with jack- et:

1. Stainless Steel: ASTM A 666, Type 304; 0.020 inch (0.5 mm) thick.

2. Aluminum:  0.007 inch (0.18 mm) thick.

3. Nickel-Copper Alloy: 0.005 inch (0.13 mm) thick.

B. Wire:  0.080-inch (2.0-mm), nickel-copper alloy; 0.062-inch (1.6-mm), soft-annealed, stainless steel; or 0.062-inch (1.6-mm), soft-annealed, galvanized steel.

2.5 VAPOR RETARDERS

A. Mastics:  Materials recommended by insulation material manufacturer that are compat- ible with insulation materials, jackets, and substrates.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine substrates and conditions for compliance with requirements for installation and other conditions affecting performance of insulation application.

B. Proceed with installation only after unsatisfactory conditions have been corrected.

3.2 PREPARATION

A. Surface Preparation: Clean and dry pipe and fitting surfaces. Remove materials that will adversely affect insulation application.

3.3 GENERAL APPLICATION REQUIREMENTS

A. Apply insulation materials, accessories, and finishes according to the manufacturer's written instructions; with smooth, straight, and even surfaces; free of voids throughout the length of piping, including fittings, valves, and specialties.

B. Refer to schedules at the end of this Section for materials, forms, jackets, and thick- nesses required for each piping system.

C. Use accessories compatible with insulation materials and suitable for the service. Use accessories that do not corrode, soften, or otherwise attack insulation or jacket in either wet or dry state.

D. Apply insulation with longitudinal seams at top and bottom of horizontal pipe runs.

E. Apply multiple layers of insulation with longitudinal and end seams staggered.

F. Do not weld brackets, clips, or other attachment devices to piping, fittings, and special- ties.

G. Seal joints and seams with vapor-retarder mastic on insulation indicated to receive a vapor retarder.

H. Keep insulation materials dry during application and finishing.

I. Apply insulation with tight longitudinal seams and end joints. Bond seams and joints with adhesive recommended by the insulation material manufacturer.

J. Apply insulation with the least number of joints practical.

K. Apply insulation over fittings, valves, and specialties, with continuous thermal and va- por-retarder integrity, unless otherwise indicated. Refer to special instructions for ap- plying insulation over fittings, valves, and specialties.

L. Hangers and Anchors: Where vapor retarder is indicated, seal penetrations in insula- tion at hangers, supports, anchors, and other projections with vapor-retarder mastic.

1. Apply insulation continuously through hangers and around anchor attachments.

2. For insulation application where vapor retarders are indicated, extend insulation on anchor legs at least 12 inches (300 mm) from point of attachment to pipe and taper insulation ends. Seal tapered ends with a compound recommended by the insulation material manufacturer to maintain vapor retarder.

3. Install insert materials and apply insulation to tightly join the insert. Seal insula- tion to insulation inserts with adhesive or sealing compound recommended by the insulation material manufacturer.

4. Cover inserts with jacket material matching adjacent pipe insulation. Install shields over jacket, arranged to protect the jacket from tear or puncture by the hanger, support, and shield.

M. Insulation Terminations: For insulation application where vapor retarders are indicat- ed, taper insulation ends. Seal tapered ends with a compound recommended by the in- sulation material manufacturer to maintain vapor retarder.

N. Apply adhesives and mastics at the manufacturer's recommended coverage rate.

O. Apply insulation with integral jackets as follows:

1. Pull jacket tight and smooth.

2. Circumferential Joints: Cover with 3-inch- (75-mm-) wide strips, of same mate- rial as insulation jacket. Secure strips with adhesive and outward clinching sta- ples along both edges of strip and spaced 4 inches (100 mm) o.c.

3. Longitudinal Seams: Overlap jacket seams at least 1-1/2 inches (40 mm). Apply insulation with longitudinal seams at bottom of pipe. Clean and dry surface to receive self-sealing lap.  Staple laps with outward clinching staples along edge at 4 inches (100 mm) o.c.

a. Exception:  Do not staple longitudinal laps on insulation having a vapor re- tarder.

4. Vapor-Retarder Mastics: Where vapor retarders are indicated, apply mastic on seams and joints and at ends adjacent to flanges, unions, valves, and fittings.

5. At penetrations in jackets for thermometers and pressure gages, fill and seal voids with vapor-retarder mastic.

P. Roof Penetrations: Apply insulation for interior applications to a point even with top of roof flashing.

1. Seal penetrations with vapor-retarder mastic.

2. Apply insulation for exterior applications tightly joined to interior insulation ends.

3. Extend metal jacket of exterior insulation outside roof flashing at least 2 inches (50 mm) below top of roof flashing.

4. Seal metal jacket to roof flashing with vapor-retarder mastic.

Q. Exterior Wall Penetrations: For penetrations of below-grade exterior walls, terminate insulation flush with mechanical sleeve seal. Seal terminations with vapor-retarder mastic.

R. Interior Wall and Partition Penetrations:  Apply insulation continuously through walls and floors.

S. Fire-Rated Wall and Partition Penetrations: Apply insulation continuously through penetrations of fire-rated walls and partitions.

3.4 MINERAL-FIBER INSULATION APPLICATION

A. Apply insulation to straight pipes and tubes as follows:

1. Secure each layer of preformed pipe insulation to pipe with wire, tape, or bands without deforming insulation materials.

2. Where vapor retarders are indicated, seal longitudinal seams and end joints with vapor-retarder mastic. Apply vapor retarder to ends of insulation at intervals of 15 to 20 feet (4.5 to 6 m) to form a vapor retarder between pipe insulation seg- ments.

3. For insulation with factory-applied jackets, secure laps with outward clinched staples at 6 inches (150 mm) o.c.

4. For insulation with factory-applied jackets with vapor retarders, do not staple longitudinal tabs but secure tabs with additional adhesive as recommended by the insulation material manufacturer and seal with vapor-retarder mastic.

B. Apply insulation to flanges as follows:

1. Apply preformed pipe insulation to outer diameter of pipe flange.

2. Make width of insulation segment the same as overall width of the flange and bolts, plus twice the thickness of the pipe insulation.

3. Fill voids between inner circumference of flange insulation and outer circumfer- ence of adjacent straight pipe segments with mineral-fiber blanket insulation.

C. Apply insulation to fittings and elbows as follows:

1. Apply premolded insulation sections of the same material as straight segments of pipe insulation when available. Secure according to manufacturer's written in- structions.

2. When premolded insulation elbows and fittings are not available, apply mitered sections of pipe insulation, or glass-fiber blanket insulation, to a thickness equal to adjoining pipe insulation. Secure insulation materials with wire, tape, or bands.

3. Cover fittings with standard PVC fitting covers.

D. Apply insulation to valves and specialties as follows:

1. Apply premolded insulation sections of the same material as straight segments of pipe insulation when available. Secure according to manufacturer's written in- structions.

2. When premolded insulation sections are not available, apply glass-fiber blanket insulation to valve body. Arrange insulation to permit access to packing and to allow valve operation without disturbing insulation. For check valves, arrange insulation for access to stainer basket without disturbing insulation.

3. Apply insulation to flanges as specified for flange insulation application.

4. Use preformed standard PVC fitting covers for valve sizes where available. Se- cure fitting covers with manufacturer's attachments and accessories. Seal seams with tape and vapor-retarder mastic.

5. For larger sizes where PVC fitting covers are not available, seal insulation with canvas jacket and sealing compound recommended by the insulation material manufacturer.

3.5 FLEXIBLE ELASTOMERIC THERMAL INSULATION APPLICATION

A. Apply insulation to straight pipes and tubes as follows:

1. Follow manufacturer's written instructions for applying insulation.

2. Seal longitudinal seams and end joints with manufacturer's recommended adhe- sive. Cement to avoid openings in insulation that will allow passage of air to the pipe surface.

B. Apply insulation to flanges as follows:

1. Apply pipe insulation to outer diameter of pipe flange.

2. Make width of insulation segment the same as overall width of the flange and bolts, plus twice the thickness of the pipe insulation.

3. Fill voids between inner circumference of flange insulation and outer circumfer- ence of adjacent straight pipe segments with cut sections of sheet insulation of the same thickness as pipe insulation.

4. Secure insulation to flanges and seal seams with manufacturer's recommended adhesive. Cement to avoid openings in insulation that will allow passage of air to the pipe surface.

C. Apply insulation to fittings and elbows as follows:

1. Apply mitered sections of pipe insulation.

2. Secure insulation materials and seal seams with manufacturer's recommended adhesive. Cement to avoid openings in insulation that will allow passage of air to the pipe surface.

D. Apply insulation to valves and specialties as follows:

1. Apply preformed valve covers manufactured of the same material as pipe insula- tion and attached according to the manufacturer's written instructions.

2. Apply cut segments of pipe and sheet insulation to valve body. Arrange insula- tion to permit access to packing and to allow valve operation without disturbing insulation. For check valves, fabricate removable sections of insulation arranged to allow access to stainer basket.

3. Apply insulation to flanges as specified for flange insulation application.

4. Secure insulation to valves and specialties and seal seams with manufacturer's recommended adhesive. Cement to avoid openings in insulation that will allow passage of air to the pipe surface.

3.6 FIELD-APPLIED JACKET APPLICATION

A. Foil and Paper Jackets:  Apply foil and paper jackets where piping is concealed.

1. Draw jacket material smooth and tight.

2. Apply lap or joint strips with the same material as jacket.

3. Secure jacket to insulation with manufacturer's recommended adhesive.

4. Apply jackets with 1-1/2-inch (40-mm) laps at longitudinal seams and 3-inch- (75-mm-) wide joint strips at end joints.

5. Seal openings, punctures, and breaks in vapor-retarder jackets and exposed insu- lation with vapor-retarder mastic.

B. Apply PVC jacket on all exposed piping. Wrap Jacket with minimum 1-inch (25-mm) overlap at longitudinal seams and end joints. Seal with manufacturer's recommended adhesive.

3.7 FINISHES

A. Color: Final color as selected by Architect. Vary first and second coats to allow visual inspection of the completed Work.

3.8 PIPING SYSTEM APPLICATIONS

A. Insulation materials and thicknesses are specified in schedules at the end of this Sec- tion.

B. Items Not Insulated: Unless otherwise indicated, do not apply insulation to the follow- ing systems, materials, and equipment:

1. Flexible connectors.

2. Vibration-control devices.

3. Drainage piping located in crawl spaces, unless otherwise indicated.

4. Below-grade piping, unless otherwise indicated.

5. Chrome-plated pipes and fittings, unless potential for personnel injury.

6. Air chambers, unions, strainers, check valves, plug valves, and flow regulators.

3.9 FIELD QUALITY CONTROL

A. Inspection: Perform the following field quality-control inspections, after installing in- sulation materials, jackets, and finishes, to determine compliance with requirements:

1. Inspect fittings and valves randomly selected by Engineer.

B. Insulation applications will be considered defective if sample inspection reveals non- compliance with requirements. Remove defective Work and replace with new materi- als according to these Specifications.

C. Reinstall insulation and covers on fittings and valves uncovered for inspection accord- ing to these Specifications.

3.10 INSULATION APPLICATION SCHEDULE, GENERAL

A. Refer to insulation application schedules for required insulation materials, vapor re- tarders, and field-applied jackets.

B. Application schedules identify piping system and indicate pipe size ranges and materi- al, thickness, and jacket requirements.

3.11 INTERIOR INSULATION APPLICATION SCHEDULE

A. Service: Domestic (W1) hot, & cold and Non-potable (W2) which are piped utilizing copper or steel or stainless steel piping. (For W1 and W2 water piped in corrosive are- as utilizing Schedule 80 CPVC – no insulation required.)

1. Operating Temperature: 50 to 140 deg F (15 to 60 deg C).

2. Insulation Material: Mineral fiber.

3. Insulation Thickness: 1 (one) inch.

4. Vapor Retarder Required: No.

5. Jacket:
a. FSK where piping is concealed;
b. PVC where piping is exposed (protects insulation from washdown activi- ties).

B. Service:  Rainwater conductors.

1. Operating Temperature: 32 to 100 deg F.

2. Insulation Material: Mineral fiber.

3. Insulation Thickness: 1/2-inch minimum.

C. Service:  Roof drain bodies.

1. Operating Temperature: 32 to 100 deg F (0 to 38 deg C).

2. Insulation Material: Mineral fiber or Flexible elastomeric.

3. Insulation Thickness: 1 inch

D. Service: Exposed sanitary drains and domestic water supplies and stops for fixtures for the disabled.

1. Operating Temperature: 35 to 120 deg F (2 to 49 deg C).

2. Insulation Material: Mineral fiber.

3. Insulation Thickness: 1 (one) inch

4. Field-Applied Jacket:  PVC P-trap and supply covers.


END OF SECTION