SECTION 40 61 93
PROCESS CONTROL
SYSTEM INPUT/OUTPUT
LIST
PART 1 - GENERAL
1.1
DESCRIPTION
A.
Scope:
1. This Section
describes
the
system
input/output
(I/O)
list Contract
deliverable
and requirements
for configuring the control
system
database.
A sample
I/O
list follows this Section. The CONTRACTOR
shall
supply a complete
and fully populated I/O list. The I/O list
shall
include all existing I/O being moved by the CONTRACTOR to the new PAC
panels and all new I/O required for this contract.
B.
Related
Sections:
1. Section 40
64 00, Programmable Automation
Controllers.
1.2
SUBMITTALS
A. For each I/O
attribute listed in the I/O
list
that cannot
be completed,
submit
an explanation of the reason for the deviation.
Do not proceed with any configuration
until a method
of resolving
deviations is accepted by the ENGINEER.
B.
Include
the PAC specific submittals
for Section 40 64 00, Programmable
Automation
Controllers.
C. CONTRACTOR shall
provide and complete
the information
requested in the sample
table,
including
identification
of
all
soft
I/O for
digital communication networks including DeviceNet, Modbus, and
Ethernet. The Listing shall include the node address, and addresses
within
the
device. The addresses shall be coordinated by the CONTRACTOR so that
node
and segment
addresses are unique within the Monitoring and Control
System.
1.3
I/O
POINT LIST DESCRIPTION
A. “TAG NO.” is
an alphanumeric
character string. The point tag shall follow the format:
[site][area]_[desc1][train][parallel]_[loop]_[desc2][train][parallel]_[para-
meter].attribute:
1.
Site –
Site designation, in lower case.
2.
Area –
The two digit process area number.
3. Desc1 – The
first descriptor field intended
for
the specific
process
description. If more
appropriate,
it may
be used for primary
equipment
name,
area, building, etc.
4.
Train
– The process train
number.
5. Parallel – The
lower case
alphabetical
designator
for
multiple
equipment
operating in parallel on a single process train.
6. Loop – The loop
number
from
the
flow diagram
or
instrument
tag. In the case of valves, this will
be the valve number.
7. Desc2 – The
second descriptor field
intended
for the equipment
or device associated with
the
tag.
8.
Parameter
– The process variable
of the
associated equipment.
9.
.Attribute
– The tag attribute of a Wonderware
object or parameter
within a
ControlLogix object.
10.
Example
– e28_inc1_xxxx_wb_psi.ind
a.
“e”
represents
the Easterly WWTP site.
b.
“28”
is the process area number
for
the Primary
Settling Tanks
c.
“inc1”
is the fluidized bed
incinerator, process train 1.
d.
“wb”
is windbox, the device
or
equipment
description. e.
“psi”
is pressure,
the process
parameter.
f.
“ind”
is the attribute
for indication. g.
“xxxx”
is the 4-digit loop number.
B. “DESCRIPTION”
is an alphanumeric
character
string
up
to
40
positions
in
length. Points described as “SPARE”
denote
pre-wired I/O.
C. “SIGNAL TYPE”
describes whether the
point is connected
through
a digital network, discrete, or analog means.
D.
“DATA
FIELD”
is a modifier
for the signal
type,
which
shows
additional
details.
E.
“RANGE
/ UNITS” lists the high and
low
ranges of the signal in engineering
units.
F.
“SET
POINT” shows the trip points of
discrete
items
such as switches.
G. “SIGNAL FROM”
lists the origin of the signal,
as related to the control panel or valve actuator, etc.
H.
“TB
NO.” is the terminal
block where the signal
originates.
I. “PANEL/DEV.
TERMINAL
NO.” is the terminal
on the panel or device from which the signal
originates.
J. “POWER
SOURCE” lists the location
of the
power source which is powering the signal.
K. “SIGNAL TO”
lists the destination of the signal, as related to the control panel
or valve actuator, etc.
L. “PLC TERMINAL
NO.” is the
terminal
in the
PLC panel which is connected
to the signal.
M. “PLC POINT
ADDRESSES” is the terminal
on the PLC module
corresponding to the signal.
PART 2 - PRODUCTS
(NOT USED)
PART 3 –
EXECUTION
3.1
I/O
CONFIGURATION
A. Implement
the control system
database
fields
in a consistent manner
by using the following procedures:
1. Use
abbreviations and acronyms
already
established in the Contract
Documents.
2. Use only an
abbreviation or an acronym
for a
word or group of words, respectively.
3. Use the same
subject and word order within data fields.
4. Use the same term
(either
phrase, word or acronym)
to denote the same
meaning.
Do not use multiple
terms
for a single meaning.
5. Use the point
names,
descriptions, logic
state descriptions,
ranges and units of measurement
exactly the same
wherever the
point is referenced.
6. Show point names
and descriptions for all point references on documentation.
7. Spell
correctly.
8. Maintain
lists of acronyms
and abbreviations
used.
3.2
I/O
HARDWARE CONFIGURATION
A. Partition the I/O
among
cards
within an I/O enclosure to provide control loop integrity.
1. Put all inputs of
the same I/O type
associated
with a
device (e.g. pump,
blower, clarifier or other
piece of equipment)
on the same
card.
2. Put all
inputs of the same I/O type for devices arranged in process trains
(e.g. a pump,
its inlet valve and its outlet
valve, or a pump
and its associated macerator)
on
the same
card or cards if
more
than
one
card is required to accommodate
the points.
3. Put all outputs
of the same
I/O type
associated
with a device or group of devices in a process train on the same
card
or cards if more
than one card is required to accommodate the points.
4. Where the
preceding
requirements
specified
in this paragraph would cause more than 20
percent
spare
points
on
a card, points for a device or process train
may
be split between
two consecutive
cards.
5. Make unused
terminals
resulting from partitioning the I/O into pre-wired
spares. Provide
pre-wired spare points
with all
cabling
and termination
internal to the PAC as
done
for other I/O points.
3.3
POINT
DATA FIELDS
A. I/O point data
fields may
be subject to review and modification
by the ENGINEER during the Shop Drawing review phase. Incorporate
changes directed
by the ENGINEER completely
into
the entire system,
at no additional
cost to OWNER,
subject to the
following
limitations:
1. Limit
the total number
of modifications
to 20
percent of the total number
of
I/O points.
2. Each unique
change will count as one modification.
For example, modifying the description, range, and engineering unit
on an analog input count as three modifications.
3. Analog input
alarm
limit
definition
will
not
be counted
as a modification.
3.4
INPUT/OUTPUT
TAGGING
A. The project
Input/Output
list
shall
indicate
all required MCS
I/O
for the project, including all hardwired I/O as well as soft I/O to
be communicated between processors over and DeviceNet, Ethernet,
and Modbus protocols. Exiating, relocated I/O and new I/O shall
both be included.
B. The I/O list
shall include
all
details
that must
be coordinated
during project implementation,
such as final node addresses and registers
for
all
I/O.
C.
The
CONTRACTOR
shall
follow the OWNER-approved
format
included herein.
The attached
sample
I/O list can
be
provided
to the CONTRACTOR in electronic form
(Microsoft
Excel) upon request.
D. For each PAC/PLC
and RIO panel, the CONTRACTOR shall submit
the required tag database submittals
as described under Section
40 61 13, in the format
attached, in both hardcopy and electronic
form
(Microsoft
Excel).
E. Each submittal
shall
include all information
coordinated with
equipment
vendors and suppliers for the systems
integration work including, but not limited
to:
1. Alarm
settings
and class
2. Terminal
block information
3. Power source
4. PLC term
no
5. Final PLC
register location
F. Additionally, for
soft I/O communicated over DeviceNet, Ethernet, and Modbus the
submittal
shall include
similar
information
coordinated
with all equipment
vendors and suppliers. For
soft I/O include, but not be limited
to:
1. Alarm
settings
and class
2. Terminal
block information
3.
Communication segment
tag
4. Node address on
segment
coordinated
with all vendors and
suppliers with equipment
on that segment.
NOTE: All Ethernet IP addresses shall be furnished and coordinated
with the
OWNER’S
IT and SCADA departments.
5. Final PLC
register location.
3.5
ATTACHMENTS
A. See attached
I/O
List Sample schedule
to be as a template
by the CONTRACTOR for
completion
of the
I/O list required
for
the Primary
Settling Tanks Rehabilitation Project.
No comments:
Post a Comment