Section 15256
INSULATED UNDERGROUND PIPING
PART 1 - GENERAL
1.1 DESCRIPTION
A. Scope: This Section specifies
pre-insulated liquid piping for direct burial installation. This
Section does not provide specifications for insulation for piping
installed in galleries, rooms, pipe chases, or exposed to view.
Fluid temperatures are limited to the range 40 degrees F to 210
degrees F.
B. Type: Insulation shall be of the
factory applied urethane foam type with a polyvinyl chloride (PVC)
jacket.
C. Performance and Service
Requirements: Insulated piping furnished under this
specification shall be suitable for direct burial or
installation in pipe trenches. Fluid temperature shall be as
listed in Section 15050. Ground temperatures will range from 35
degrees F to 70 degrees F, and the piping may be installed below the
water table.
D. Design Requirements: Minimum
insulation thicknesses, exclusive of jacket, shall be as follows:
-
Pipe O.D., Inches
InsulationThickness, Inches
2 or smaller
1 inch
3 through 6
1-1/2 inches
8 through 12
1-1/2 inches
A minus 15 percent tolerance, on
the insulation thicknesses listed above, shall be permitted for
manufacturers' standard insulation systems.
1.2 REFERENCES
A. This Section contains references to
the following documents. They are a part of this Section as
specified and modified. In cases of conflict between the
requirements of this specification and those of the listed documents,
the requirements of this specification shall prevail.
ANSI B31 70 Code for Pressure
Piping
ASTM C591 85 Unfaced Preformed
Rigid Cellular Polyurethane Thermal Insulation
ASTM D1784 90 Rigid Poly
(vinylchloride); (PVC) Compounds and Chlorinated Poly
(vinylchloride) (CPVC) Compounds
ASTM D234181 Rigid Urethane Foam
1.3 SUBMITTALS
A. The following submittals
shall be provided in accordance with Section 01300:
1. Dimensioned shop drawings and
location of each expansion loop, including clearances provided
for carrier pipe expansion.
2. A
complete description of the preinsulated piping and accessories in
sufficient detail to demonstrate compliance with these
specifications.
3. A copy of this Section with addenda
updates, and all referenced sections with addenda updates, with each
paragraph check marked to show specification compliance or marked to
show deviations.
PART 2 - PRODUCTS
2.1 ACCEPTABLE MANUFACTURERS
A. Preinsulated piping systems shall be
Ric-Wil, Thermal Pipe Systems Weldtite, or equal, modified as
necessary to provide the specified performance and features.
2.2 MATERIALS
A. Carrier Pipe: Unless
otherwise specified, carrier pipe materials shall be as specified in
Section 15050, Piping Systems
Specification Sheets, for each piping system.
B. Urethane Foam Insulation:
The urethane foam shall conform to ASTM C591, Type II.
C. Insulation Jacket: All PVC shall
conform to ASTM D1784, Class 12454-B. The minimum jacket thickness
shall be 60 mils and shall be suitable for H-20 highway loading with
2 feet of cover.
D. Shrinkable Sleeves: Shrinkable
sleeves for field joints shall be compatible with the PVC
jacket. Shrinkable sleeves shall be fabricated from radiation
cross-linked semirigid polyethylene, coated on all inside surfaces
with thixotropic adhesive designed to flow and provide a complete
seal when heated.
2.3 MANUFACTURING
A. General: Pipe sections shall be
prefabricated in such a way that the urethane completely fills the
annular space between the carrier pipe and the PVC jacket. The
exposed insulation at the end of each section shall be sealed with a
factory-applied, high temperature, watertight sealant. The carrier
pipe shall extend a minimum of 6 inches beyond the insulation for
field welding.
B. Anchors: Anchor plates
shall be factory fabricated and welded to the carrier pipe. The
PVC jacket shall extend up to the
anchor plate and be factory sealed to the anchor plate.
C. Fittings: Fittings shall be
factory fabricated and pre-insulated with urethane foam
insulation. The insulation shall be protected with a PVC plastic
jacket of the same thickness and quality as that of the straight
pipe. All miters on the PVC jacket at fittings shall be welded by a
thermal set welding process to provide a continuous jacket integrity.
D. Expansion Elbows and Loops:
Prefabricated elbows, expansion loops, and tees shall be provided,
where specified. All pre-insulated fittings that must provide
compensation for pipe expansion and/or contraction shall be
installed in a suitably sized jacket and insulated with
flexible polyurethane foam insulation. The straight units adjoining
expan- sion fittings shall also be insulated with flexible
polyurethane foam insulation to compensate for lateral pipe movement.
E. End Seals: End seals shall
be provided on ends of each section of preinsulated pipe.
The end seals shall be watertight to
protect the exposed insulation.
2.4
PRODUCT DATA
A. The following information
shall be provided in accordance with Section 01300:
1. Manufacturer's certification
in accordance with Paragraph 15256-3.6.
2. Certification that the
jacket meets the requirement of Paragraph 15256-2.2 C.
3. Manufacturer's recommended field
installation instructions including pipe jointing techniques, joint
insulation, and jacket sealing.
PART 3 - EXECUTION
3.1 GENERAL
A. The preinsulated piping system
shall be installed in strict accordance with the
manufacturer's recommendations.
3.2 FIELD TESTING
A. Prior to insulating any field
joints, individual pipe sections shall be hydrostatically tested at
the test pressure and temperature indicated in Section 15050. The
Construction Manager shall be notified in writing 48 hours prior to
testing. Any leaks shall be repaired, and the system shall be
retested until no leaks are detected by the Construction
Manager. Field joints shall be insulated after hydrostatic testing
has been completed.
3.3 EXPANSION LOOPS AND ELBOWS
A. Prefabricated expansion
loops shall be located in the locations shown on the drawings.
Field fabricated expansion loops will
not be accepted.
3.4 FIELD JOINTS
A. Carrier pipe field joints shall be
as specified in Section 15050. After jointing and pressure testing,
rigid urethane insulating material or foamed-in-place urethane
of the same density and thickness as the pipe section shall
be applied to the joint area. The insulation shall be sealed
to the PVC jacket using heat shrinkable sleeves. All material used
to insulate and seal field joints shall be supplied by the piping
system manufacturer.
3.5 ANCHOR BLOCKS
A. Concrete anchor blocks shall be
provided at locations shown on the drawings. Concrete shall comply
with Section 03300. Anchor blocks shall be poured against
undisturbed soil and shall have minimum dimensions as shown on the
drawings. Pipe joints encased in anchor blocks shall be pressure
tested prior to pouring anchor blocks. No valves shall be encased in
anchor blocks.
3.6 FACTORY REPRESENTATIVE
A. A qualified factory
representative of the piping system shall be present during
the initiation of the buried piping installation, during major field
relocations or changes, and during piping system testing. The
factory representative shall supervise the pipe installation, joint
insulation process, and installation of the protective jacket at
joints during the two days of installation. On completion and
testing of the work, the Contractor shall provide a certificate from
the manufacturer stating that the installation, including any field
relocation or modifications to the system, has been made in
accordance with the manufacturer's recommendations.
END OF SECTION
No comments:
Post a Comment