Section 16075
ELECTRICAL IDENTIFICATION NAMEPLATES
AND WARNING SIGNS
PART 1 - GENERAL
1.1 THE REQUIREMENT
A. The Contractor shall furnish all
tools, equipment, material, and supplies and perform all labor
required to install nameplates and/or warning signs to identify
electrical equipment as indicated on the drawings and specified
herein.
1.2 RELATED WORK SPECIFIED
ELSEWHERE
A. The requirements of the
following sections and divisions apply to the work of this Section.
B. Other sections of the Specifications, not referenced
below, shall also apply to the extent
required for proper performance of this
work.
1. Division 11 Equipment,
Applicable Sections
2. Division 16 Electrical,
Applicable Sections
3. Division 17 Instrumentation
and Control, Section 17300
1.3 REFERENCE SPECIFICATIONS,
CODES AND STANDARDS
A. All work specified herein shall
conform to or exceed the applicable requirements of the referenced
portions of the following publications to the extent that the
provisions thereof are not in conflict with other provisions of these
specifications.
B. Comply with the current
provisions of the following codes and standards.
1. Codes and Standards
NFPA
National Fire Protection Agency (NFPA) – 70
National Electrical Code (NEC), latest
adopted version
NEC National Electrical Code (NEC),
latest adopted edition
OSHA
Occupational Safety and Health Administration
(OSHA) California Code of Regulations
Owner Tagging Procedure Owner
standards for instrument and equipment identification and tagging
Specification 17075
Valve, Panel, and Instrument Nameplates
PART 2 -
PRODUCTS
2.1 NAMEPLATES AND WARNING SIGNS
A. Nameplates: All nameplates shall be
black lamicoid with white letters of approved size when located
indoors, and shall be engraved stainless steel when located outdoors,
and shall be fastened to the device or enclosure with round head,
stainless steel screws. Any equipment for which a nameplate is
required, but without a contract document designation shall be
identified in accordance with the Owner Tagging Procedure. Contact
the Engineer for help in establishing the correct designation. See
Section 17300 for detailed information on material, thickness, size,
hole size, and mounting.
1. All switchgear, switchboards,
distribution panels, lighting panels, unit substations, transformers,
MCCs, control panels, etc. shall have nameplates in accordance with
the designations given on the Contract Documents. The nameplates
shall be installed on the front and back of the enclosure (if
backside access is available) to clearly identify each compartment,
power source, etc. This shall apply to all equipment installed and/or
modified per these Contract Documents.
2. All switchgear, MCCs and
lighting panels shall have a large nameplate with
3/4-inch high letters for the
designation given on the Contract Documents single- line diagrams.
All motor controllers or individual units within MCCs and
switchgear shall have a nameplate with ¼-inch high letters showing
the circuit number and equipment designation in accordance with the
Contract Documents single-line diagrams.
3. All control panels and
terminal board panels shall have large nameplates with
3/4-inch high letters for the panel
designation, and nameplates with 3/16-inch high letters for each
control and indicating device in accordance with the Contract
Documents.
4. Visible, permanent engraved
nameplates shall be provided identifying each instrument,
instrument switch, meter, relay, control switch, indicating light,
circuit breaker compartment, potential transformer compartment, fuse
block, and auxiliary compartment. Equipment and terminal blocks
within control panels, boxes and compartments shall be permanently
identified with engraved nameplates. This shall include the
backside of door- or panel-mounted items. The backside engraved
nameplate shall read the same as the front engraved nameplate.
Protective relays shall be designated as to use, the phase to which
connected and shall include the ANSI C 37.2 device function
number; e.g., Phase A Overcurrent Relay, Device 51.
B. Warning Signs: All warning signs
shall be in accordance with Occupational Safety and Health
Administration (OSHA) regulations and shall be suitable for exterior
use when installed outdoors. The warning signs shall be fastened
with round head, Type 316 stainless steel screws or bolts, located
and mounted in a manner acceptable to the Engineer. All warning
signs shall be 7 inches high by 10 inches wide unless otherwise
noted, and on 1/16-inch thick plastic or similar acceptable material.
The signs specified below shall be installed on the front and back of
the enclosure (if backside access is available to the enclosure)
of each electrical distribution equipment and control equipment
to clearly identify each compartment, power source, etc. This shall
apply to all equipment installed and/or modified per these Contract
Documents.
1. Permanent
and conspicuous warning signs shall be mounted on all equipment,
doorways to equipment rooms, pull boxes, manholes, etc. where the
operating voltage exceeds 600 V. High voltage warning signs shall
be colored red and white and shall read:
DANGER
480 VOLTS KEEP OUT
2. Rear access panels or doors of
cubicles containing power conductors shall include a large
“DANGER 480 VOLTS INSIDE” nameplate of red background and 1 inch
high minimum white lettering.
3. A door-mounted sign made of
laminated plastic with white letters on a red background shall
be provided on each compartment in which multiple voltage sources
will be terminated. The sign shall read: "Caution - This Unit
Contains Foreign Voltage Sources."
4. Permanent warning signs shall be
mounted at all mechanical equipment which can be started
automatically or be started from remote locations. Automatic or
remote controlled equipment warning signs shall be colored yellow and
black and shall read:
CAUTION
THIS EQUIPMENT STARTS AUTOMATICALLY OR
BY REMOTE CONTROL
5. Provide arc-flash warning labels as
follows on all new and existing electrical distribution equipment.
The warning labels shall be provided for each switchgear,
switchboard, panelboard, enclosed circuit breakers, and motor
control center (MCC). The labels shall be incompliance with NFPA 70E
listing clothing requirements, shock hazard boundaries, and PPE
requirements similar to below example:
-
Arc Flash Hazard Boundary (Dc)
7.2 ft
Incident Energy (Ed)
15.8 cal/cm2
Working Distance
18.0 in
Shock Hazard Exposure
480 VAC
Shock Hazard when covers removed
Class 00 Insulating Gloves
V-rating
500 VAC
Limited Approach Boundary
3.5 ft
Restricted Approach Boundary
1.0 ft
Prohibited Approach Boundary
0.1 ft
Source Protective Device
STS400
Equipment
MCC-STS
Hazard Category
3
Minimum PPE Requirements
A total clothing system consisting of FR shirt andpants and/or FR coveralls and/or arc flash coat and pants (clothing system minimum arc rating of 40)
2.2 CIRCUIT IDENTIFICATION
A. Raceway Identification: All
raceways, any channel, conduit, etc. that is greater than 50 feet in
length or where conduit terminations are out of sight from each other
designed for holding wires, cables or bus bars, shall be tagged at
all terminations. The numbering system to identify raceways shall
consist of two parts. Example: P137-P103. P137 indicates Job No.
P1-37; the same Job No. is used for all conduit installed by the
project. P103 indicates the unique designation as shown on
the drawings or the conduit schedule. .
1. Raceway marker tags shall be
0.036-inch minimum thickness, be made of solid brass and the raceway
number shall be stamped in 3/16-inch minimum height characters. Tags
shall be attached to the raceway with Type 316 stainless steel wire.
2. All exposed raceways with conductors
rated greater than 600 V shall be marked every 30 feet with 1-inch
high letters indicating the actual system operating voltage
(e.g., 12,470 Volts). Labels shall be vinyl plastic as manufactured
by Brady, Seton, or equal.
B. Conductor and Cable Tags
1. Conductor and Cable Identification:
Each cable or conductor shall be identified with circuit
identification markers in each pull box, manhole, panelboard, cable
tray or termination. Each cable or conductor shall be identified
with an approved, yellow or white tubing-type shrink-on wire marker.
The color white is used except yellow tubing shall be installed on
conductors that bring foreign voltage into the panel. Note that there
may be a white wire tag at the source end and a yellow tag at the end
where the conductor would be considered to have a foreign voltage.
The wire sleeve should only be slightly shrunk to keep the tubing
from slipping down the wire but loose enough to allow the wire tag to
be rotated after it is installed so it can be made more readable.
Tags relying on adhesives or taped- on markers are not acceptable.
The cable marker will consist of two elements:
1) A FROM-TO line showing the
termination enclosures for each end of the cable and 2) a two-part
number with the first part the Job No. and the second part the Cable
Schedule ID. The conductor marker will consist of three elements: 1)
The immediate terminal number, 2) a ">", and 3) the
destination panel, terminal block and terminal number. See Owner
Example Contractor-furnished Interconnection Wiring Diagram with Wire
and Cable Tag Standard for an example drawing. Cables shall also be
tagged at all jacket end points and within 12 inches of entering a
conduit from a cable tray. This identification is applicable to all
power, control, alarm, and instrumentation conductors, and
shall correspond to the single-line diagram circuit numbers and
signal cable pair designations shown on the Contract Documents.
2. Manufacturer
a. Individual conductor identification
markers shall be slip-on PVC type, as manufactured by Brady, Thomas
and Betts, or equal.
b. Markers for other cables shall be
B-292 or B-500 vinyl as manufactured by Brady, Thomas and Betts, or
equal.
C. Clear
identification of each compartment, power source, etc. shall be
provided on the front and back of the electrical distribution
equipment enclosures and control panel enclosures. This shall apply
to all equipment installed and/or modified per these Contract
Documents.
D. Color Coding: The three-phase
conductors for power circuits shall be identified at each manhole,
pull box and at all switchgear, panelboards, motor
control centers, switchboards, etc. as Phases A, B and C. Phase A
shall be brown, Phase B shall be orange, and Phase C shall be yellow.
The neutral conductor shall be white.
PART 3 - EXECUTION
3.1 GENERAL
A. The Contractor shall coordinate the
installation of electrical equipment so all equipment is identified
in accordance with these specifications.
END OF SECTION
No comments:
Post a Comment