Section 16060
GROUNDING AND BONDING
PART 1 - GENERAL
1.1 THE REQUIREMENT
A. The Contractor shall furnish all
tools, equipment, materials, and supplies and shall perform
all labor required to complete the work as indicated on the
drawings and specified herein.
B. Electrical grounding and bonding
systems shall be installed as indicated herein and/or on the other
Contract Documents with materials including, but not limited to,
cables/wires, connectors, solderless lug terminals, grounding
electrodes and plate electrodes, bonding jumper braid, exothermic
connections, and additional accessories needed for a complete
installation. Where materials or components are not indicated,
provide products which comply with NEC, UL, and IEEE requirements and
with established industry standards.
C. System ground conductors shall run
continuously in duct banks and cable trays, through manholes,
handholes, and other raceways. The system ground conductor shall
be connected to the structure grounding systems to provide a
continuous ground system.
1.2 RELATED WORK SPECIFIED
ELSEWHERE
A. The requirements following
divisions and sections applies to the work of this Section.
1. Section 01660
2. Division 11
3. Division 15
4. Division 16
5. Division 17
B. Materials, equipment and devices
furnished and installed under Contracts with raceway and electrical
conductors furnished, installed, and connected under Division
16, Electrical.
1.3 REFERENCED SPECIFICATIONS,
CODES AND STANDARDS
A. All work specified herein shall
conform to or exceed the applicable requirements of the referenced
portions of the following publications to the extent that the
provisions thereof are not in conflict with other provisions of these
specifications.
B. Comply with the current
provisions of the following Codes and Standards.
1. Codes and Standards
NEC
National Fire Protection Agency (NFPA) – 70 National
Electrical Code (NEC), latest adopted
version
CCR
Title 8, Industrial Relations, Subchapter
5, Electrical
Safety Orders, California Code of
Regulations.
2. Commercial Standards
ANSI/IEEE 80 Guide for
Safety in AC Substation Grounding
ANSI/UL 467 Safety
Standard for Grounding and Bonding Equipment
IEEE 142
Grounding of Industrial and Commercial Power Systems
C. All equipment furnished by the
Contractor shall be listed by and shall bear the label of
Underwriters' Laboratories, Incorporated, (UL) or of an independent
testing laboratory acceptable to OCSD.
D. The construction and installation of
all electrical equipment and materials shall comply with all
applicable provisions of the CAL OSHA Safety orders. (Title 8 CCR,
as applicable), State Building Standards, and applicable local codes
and regulations.
1.4 CONTRACTOR SUBMITTALS
A. Submittals shall be made in
accordance with the requirements of Section 16010.
B. General Provisions: Submittals
shall conform to the requirements of Section 16080, Section 16120 and
additional requirements specified herein. Submittals shall be made
for, but not be limited to the following:
1. Catalog literature for all
products.
2. Certified copies of ground
test results.
3. Field test procedures
including lists of test equipment to be used.
1.5 QUALITY ASSURANCE
A. Quality assurance shall be
in accordance with the requirements of Section 16010 and
Section 16080.
PART 2 - PRODUCTS
2.1 GROUND RODS
A. Provide copper ground rods not less
than 3/4 inch in diameter, 10-feet long driven full length into the
earth. Special requirements shall be as shown and as specified
herein. In chemical areas stainless steel rods 3/4" shall be
used.
2.2 GROUND CONDUCTORS
A. Provide grounding conductors
of the size shown and the type specified in Section 16120.
In no case shall the size of any
grounding conductor be less than that stipulated by the
NEC for that specific application.
B. All grounding conductors
furnished shall be composed of material resistant to any
existing corrosive conditions or shall be suitably protected against
such conditions.
2.3
GROUND CONNECTIONS
A. For below grade connections,
provide exothermic-welded connectors. B. For above grade
connections, provide bolted connectors.
C. Embed all conduits in
betonite, 6” all sides of conductor.
PART 3 - EXECUTION
3.1 GENERAL
A. The grounding electrode system
shall consist of concrete encased, bare #2/0 AWG copper ground
conductors and/or ground rods. Each duct bank shall contain a
concrete encased, bare #2/0 AWG system ground conductor.
B. The UFER concrete-encased ground
conductor shall be at least 20 feet in length and laid in a straight
line located approximately two-inches above the bottom of the
concrete pour.
C. Each metallic raceway, panel,
switchboard, and other metallic devices associated with the
electrical and instrumentation systems shall be bonded to this
system. All equipment enclosures, devices, etc. shall be grounded.
D. Ground rods shall be driven or
concrete encased bare copper conductors installed before a building
or structure is built, and ground conductors shall be brought through
the concrete to accessible points for grounding equipment via a
schedule 40 PVC pipe sleeve. Each structure or building where
switchgear, MCCs, switchboards, panelboards, etc. is installed shall
have a ground system.
E. Driven ground rods stainless
steel ¾-inch diameter by 10 feet in length.
F. All connections of ground cable to
rods or to cable shall be by means of exothermic welded connections
or compression connectors or bolted as indicated in Section 2.3.
G. The Contractor shall ground the
electrical service system neutral at the service entrance equipment
to the grounding electrode system and ground each separately
derived system, including the UPS, neutral to the nearest effectively
grounded structural steel member or the grounding electrode system.
H. The Contractor shall connect
together service equipment enclosures, exposed noncurrent
carrying metal parts of electrical equipment, metal raceway
systems, grounding conductor in raceways and cables, receptacle
ground connectors, and plumbing systems as required by Section
250-80 of the National Electrical Code.
I. Unless otherwise indicated on the
Contract Documents, the Contractor shall provide electrical grounding
conductors for grounding system connections that match power supply
wiring materials and are sized according to NEC. All equipment
grounding conductors shall consist of a separate insulated equipment
grounding conductor run in the conduit or multiconductor cable from
the equipment to the MCC, panelboard, switchgear, etc. equipment
ground bus. A separate equipment grounding conductor, in addition to
the cable shields, shall be provided in each raceway containing
medium voltage power cables.
J. The
Contractor shall terminate feeder and branch circuit insulated
equipment-grounding conductors with grounding lug, or bushing.
K. The Contractor shall connect
together metal raceway systems, cable tray systems, and grounding
conductors in raceways and cables, as required by Section 250-80 of
the National Electrical Code. The cable tray ground cable shall be
sized for the largest circuit breaker serving the cable tray system.
L. The Contractor shall tighten
grounding and bonding connectors and terminals, including screws and
bolts, to the manufacturer's recommended torque values. Where
manufacturer’s torque values do not exist, comply with torque
values specified in UL
486A.
M. Except where specifically indicated
otherwise, ground all exposed noncurrent-carrying metallic parts of
electrical equipment, raceway systems, and the neutral of all wiring
systems in strict accordance with the state, and other applicable
laws and regulations.
N. Where grounding conductors are
shown, bond the wires to metallic enclosures at each end and to all
intermediate metallic enclosures. Connect grounding conductors to
all grounding bushings on raceways. Where any equipment contains a
ground bus, extend and connect grounding conductors to that bus.
Connect the enclosure of the equipment containing the ground bus to
that bus. Use insulated ground conductors when ground conductor is
installed inside conduits enclosing the power conductors.
O. Ground connection to equipment and
ground buses shall use ground lugs compatible with copper.
Connections to enclosures not provided with ground buses or ground
terminals shall be by clamp type lugs added under permanent assembly
bolts or under new bolts drilled and added through enclosures other
than explosion proof, or by grounding locknuts or bushings.
Explosion proof enclosures not provided with any of the above
grounding means shall be grounded by the addition of an adjacent
junction box with a ground lug. Ground cable connections to anchor
bolts, against gaskets, paint, or varnish, or on bolts holding
removable access covers will not be permitted.
P. Install sufficient ground rods in
addition to code required grounding so that resistance to ground as
tested by standard methods does not exceed 1 ohm unless
otherwise accepted. Where more than one rod is required, install
rods at least 6-feet apart.
Q. Ground shields of any shielded power
cable at each splice or termination in accordance with
recommendations of the splice or termination manufacturer. Ground
shields of any control cables in accordance with the details shown.
R. Ground metal sheathing and
any exposed metal vertical structural elements of buildings.
Ground metal fences enclosing
electrical equipment. Bond any metal equipment platforms which
support electrical equipment to that equipment. Provide good
electrical contact between metal frames and railings supporting
pushbutton stations, receptacles, instrument cabinets, etc., and
raceways carrying circuits to these devices.
S. Bond neutrals of transformers within
buildings to the system ground network, or to any additional
indicated grounding electrodes.
T. Ground cable penetrations through
building exterior walls shall enter within 3 feet below finish grade
and shall be prepared with a water stop. Unless otherwise
indicated, the water stop shall include filling the space between the
strands with solder and soldering a
12 inch copper disc over the cable.
U. Ground
cable near the base of a structure shall be in earth and as far from
the structure as the excavation permits but not closer than 6 inches.
V. The main grounding conductor when
exposed within a building shall be copper bar supported with
suitable spacers to one inch from the structure. Unless
otherwise indicated on the drawings, the ground bus shall not be
smaller than 1/4 by one inch rectangular.
W. Lighting fixtures and convenience
outlets shall be grounded with a separate ground conductor.
X. The grounding system shall be bonded
to station piping by connection to the first flange inside the
building on either a suction or discharge pipe which will form a good
ground connection. The connection shall be made with a copper bar
or strap by drilling and tapping the flange and providing a bolted
connection.
Y. Ground conductors on equipment shall
be formed to the contour of the equipment and firmly supported.
250-92-C2 ex. #6 wire and larger shall be in a raceway to prevent
physical damage.
Z. All ground connection hardware,
bolts, and nuts shall be high strength, high conductivity copper
alloy.
AA. Ground cables with encased
underground conduit banks shall be as indicated on the drawings.
BB. Ground cables in underground
circuits shall be bonded with main ground cables in each maintenance
hole and handhold. Maintenance hole hardware and cover shall be
effectively grounded.
CC. Liquid tight flexible conduits
shall be provided with separate equipment grounding conductors
sized in accordance with the NEC. The equipment grounding conductor
shall be bonded to an approved grounding bushing and terminal lug.
The grounding conductor can be installed outside the conduit if the
required size is greater that No. 10.
DD. Exposed splices and connections
for bare copper conductors and buses shall be protected by
wrapping with heat shrink tape or covering.
3.2 GROUNDING CONNECTIONS
A. Unless shown otherwise, make
connections of grounding conductors to ground rods at the upper end
of the rod with the end of the rod and the connection point below
finished grade.
B. Make connections of sections of
outdoor ground mats (counterpoise) for substations or other
equipment underground. Make connections of other grounding
conductors generally accessible.
C. In manholes, install ground rods
with ends 4 to 6-inches above the floor with connections of grounding
conductors fully visible and accessible. Contractor shall bury at
least 8 feet of rod.
D. When
making exothermic welds, wire brush or file the point of contact to a
bare metal surface. Use exothermic welding cartridges and molds in
accordance with the manufacturer's recommendations. After welds have
been made and cooled, brush slag from the weld area and thoroughly
clean the joint.
E. Use connectors of proper size for
conductors and ground rods specified. Use connector manufacturer's
compression tool. Notify the Engineer and the Inspector
prior to backfilling any ground connections.
3.3 FIELD TESTS
A. The grounding system shall
be tested in accordance with Section16080.
END OF SECTION
My cousin recommended this blog and she was totally right keep up the fantastic work!!
ReplyDeleteNec phone in Canada - Nec DTerm phones