Section 16050
BASIC MATERIALS AND METHODS
PART 1 - GENERAL
1.1 THE REQUIREMENT
A. The Contractor shall furnish all
tools, equipment, materials, and supplies and shall perform
all labor required to complete the work as indicated on the
Drawings and specified herein.
B. This Section covers the work
necessary to furnish and install, complete, the materials specified
hereinafter.
1.2 RELATED WORK SPECIFIED
ELSEWHERE
A. The requirements of the
following sections and divisions applies to of this Section.
1. Section 09800
2. Section 16010
3. Division 17
4. Work Specified Under Other
Divisions
a. All concrete work required for
encasement, installation, or construction of the work specified in
the various sections of Division 16 is included as a part of the work
hereunder, and shall be 2500-psi concrete conforming to the
applicable requirements of Section 03300, provided that the following
exceptions and supplementary requirements shall apply:
(1) Consolidation of encasement
concrete around duct banks shall be by hand puddling, and/or no
mechanical vibration.
(2) A workability admixture shall be
used in encasement concrete, which shall be a hydroxylated carboxylic
acid type in liquid form. Admixtures containing calcium chloride
shall not be used.
(3) Concrete for encasement of conduit
or duct banks shall contain an integral red-oxide coloring pigment in
the proportion of 8 pounds per cubic yard of concrete.
B. Materials and equipment furnished
and installed under other Divisions with raceway and electrical
conductors furnished, installed and connected under Division 16,
Electrical.
1.3 REFERENCE SPECIFICATIONS,
CODES AND STANDARDS
A. All work specified herein shall
conform to or exceed the applicable requirements of the referenced
portions of the following publications to the extent that the
provisions thereof are not in conflict with other provisions of these
specifications.
1.
Codes and Standards
NEC
National Fire Protection Agency (NFPA) – 70 National
Electrical Code (NEC), latest adopted
version
CCR Title
8, Industrial Relations, Subchapter 5, Electrical
Safety Orders, California Code of
Regulations
2. Government Standards
FS W-C-596E/GEN(1) Connector, Plug,
Receptacle and Cable Outlet, Electrical
Power
FS W-S-896E/GEN(1) Switches, Toggle
(Toggle and Lode), Flush Mounted
(ac)
FS WW-C-581E Conduit,
Metal, Rigid, and Intermediate; and Coupling, Elbow, and Nipple,
Electrical Conduit: Steel, Zinc Coated
3. Commercial Standards
ANSI B16.5 Pipe
Flanges and Flanged Fittings, Steel, Nickel Alloy, and Other Special
Alloys
ANSI C80.1
Specification for Rigid Steel Conduit, Zinc Coated ANSI Z55.1
Gray Finishes for Industrial Apparatus and Equipment
ANSI/UL 467 Safety Standard for Grounding and Bonding
Equipment NEMA WD-1-1.10 General Requirements for Wiring
Devices
NEMA AB-1 Molded Case
Circuit Breakers
NEMA PB-1 Panelboards
NEMA KS-1 Enclosed
Switches
NEMA VE-1 Ventilated
Cable Tray
ICEA S-61-402
Thermoplastic - Insulated Wire and Cable for the
Transmission and Distribution of
Electrical Energy
ICEA S-19 Rubber -
Insulated Wire and Cable for the Transmission and Distribution of
Electrical Energy
UL 943 Ground
Fault Circuit Interrupters
B. All equipment furnished by the
Contractor shall be listed by and shall bear the label of
Underwriters' Laboratories, Incorporated, (UL) or of an independent
testing laboratory acceptable to the Owner.
C. The
construction and installation of all electrical equipment and
materials shall comply with all applicable provisions of the Cal/
OSHA Safety Orders (Title 8, CCR), State Building Standards, and
applicable local codes and regulations.
1.4 CONTRACTOR SUBMITTALS
A. Submittals shall be made in
accordance with the requirements of Section 16010.
1.5 QUALITY ASSURANCE
A. Quality assurance shall be
in accordance with all applicable requirements of Section
16010.
PART 2 - PRODUCTS
2.1 SERVICE ENTRANCE
A. Provide labor and furnish equipment
as required by the electric utility, which will provide service to
the facility. All such materials and work shall meet the
requirements of the utility company.
B. Provide temporary service for
construction tools and testing apparatus during
construction.
2.2 HAZARDOUS AREAS
A. Provide devices, materials, and
equipment for installation in hazardous areas that are specifically
approved for installation in hazardous areas of the Class, Division,
and Group indicated, and are of construction that will ensure safe
performance under conditions of proper use and maintenance. Provide
devices, materials, and equipment meeting the requirements of the
NEC, applicable state and local codes, and the authority enforcing
these codes. Acceptable manufacturers: Crouse-Hinds, Appleton, or
equal.
2.3 OUTLET AND DEVICE BOXES
A. General: Provide boxes not
less than 2-inches deep, unless shallower boxes are required
by structural conditions and are specifically accepted by the
Engineer. Do not use box extensions to provide wiring space required
by the NEC. For hollow masonry construction, provide boxes of
sufficient depth so that conduit knockouts or hubs are in the masonry
void space.
B. Sheet Steel (SS) Boxes: Provide
zinc- or cadmium-plated boxes of the one-piece drawn type. Install
4-inch minimum octagonal boxes for ceiling outlets, except where
smaller boxes are required for the particular fixture being
installed. Use concrete type boxes in poured concrete slabs.
Provide 4-inch by 4-inch minimum boxes with 3/4" knockouts for
switches and receptacles. Provide plaster rings where required.
C. Cast Steel (CS) Boxes: Provide
boxes of cast ferrous metal with gasketed, watertight, cast ferrous
metal covers and 316 stainless steel screws. Provide boxes with
threaded conduit hubs and cast mounting lugs where lugs are required.
Use Crouse-Hinds or Appleton Type FS or FE boxes, or equal.
D. Cast
Aluminum (CA) Boxes: Provide boxes of cast, copper-free aluminum
with gasketed, watertight, cast copper-free aluminum covers and 316
stainless steel screws. Provide boxes with threaded conduit hubs and
cast mounting lugs where lugs are required. Use Crouse-Hinds or
Appleton Type boxes, or equal.
E. Nonmetallic (NM) Boxes:
Provide fiberglass boxes with gasketed, watertight covers and
316 stainless steel screws. Provide
boxes with conduit hubs and any required mounting lugs. Use
Crouse-Hinds Stahlin or equal.
F. Provide a box suitable for the
conditions encountered at each outlet in the wiring or raceway system
and sized in accordance with the NEC. Use the listed types unless
otherwise indicated or accepted.
G. Unless otherwise indicated on the
Contract Documents, device boxes and junction boxes shall be heavy
duty, 316 stainless steel and shall be compatible with the location
and conduit system being used, and shall be manufactured by
Crouse-Hinds, Appletion, or equal, with 316 stainless steel cover
screws and with cover gaskets. Device boxes shall be “FD” type.
1. Types to be provided, PVC-coated
Steel Raceway System: Locations
Box Type
All Carbon steel sheet not less
than No.14 gauge thick
2. Exterior Locations, with:
Exposed Raceways
316 stainless steel (NEMA 4X) Concealed Raceways
316 stainless steel (NEMA 4X) Concrete Encased Raceways
316 stainless steel (NEMA 4X) Class I, II, or III Hazardous Areas
Cast steel, NEMA 7
3. Interior Dry Locations,
with:
Exposed Rigid Conduit
Sheet metal Concealed Raceways Sheet steel
Concrete Encased Raceways Cast steel Lighting Circuits,
Ceiling Portion Sheet steel
Class I, II, or III Hazardous Areas
Cast steel, NEMA 7
4. Interior Wet Locations,
with:
Exposed Raceways
316 stainless steel (NEMA 4X) Concealed Raceways
Cast steel
Concrete
Encased Raceways Cast steel
Lighting Circuits, Ceiling Portion
Sheet steel
Class I, II, or III Hazardous Areas
Cast steel, NEMA 7
5. Types to be Provided, Nonmetallic
Raceway System: Locations
Box Type
All
Nonmetallic Exposed Raceways
Nonmetallic Concealed Raceways Nonmetallic
Concrete Encased Raceways Nonmetallic
H. Device Plates: Types to be
provided:
Locations
Plate Type
All
Metal All Interior
Metal Office
Plastic
WP Designation
Weatherproof
Interior
(Except those designated WP) Flush Mounted Boxes
Metal
Surface Mounted Cast Metal Boxes
Cast metal
Surface Mounted Sheet Metal Boxes
Metal
2.4 JUNCTION AND PULL BOXES
A. Utilize NEMA 4X 316 stainless steel
for outdoor or wet and corrosive locations and where subscript WP is
indicated at the box location on the Drawings.
B. Where outlet boxes are used as
junction or pull boxes, use materials as specified under article 2.3,
OUTLET AND DEVICE BOXES.
C. Where larger sheet steel boxes are
required, utilize boxes of code-gauge, galvanized steel with
full-access screw covers mounted with corrosion-resistant machine
screws.
D. Where larger cast metal
boxes are required, use neoprene gasketed, watertight boxes with
hinged, cast metal full-access covers, 316 stainless steel cover
hardware, and drilled and tapped conduit entrances. Use
Crouse-Hinds Series W, O.Z./Gedney Series Y boxes, or equal. For
below grade conduit, use Crouse-Hinds Type WJBF, O.Z./Gedney
Series YR,
or equal, minimum size 8-inches by 8-inches by 6-inches. For
hazardous areas, use boxes applicable for the location and hazardous
atmosphere present.
E. Where larger nonmetallic boxes
are required, they shall be gasketed, watertight, corrosive
resistant, and have a hinged, full-access screw cover. The hinge and
machine screws shall be 316 stainless steel. The box and cover shall
be of high impact strength fiberglass-reinforced polyester material
with stability to high heat. The boxes shall have conduit hubs and
any required mounting lugs. The minimum size shall be 7-inches by
10-inches by 6-1/2-inches deep. Use
Crouse-Hinds, or equal, Type NJB boxes.
F. Use concrete boxes of reinforced,
cast concrete, 10-inches by 17-inches minimum inside dimensions,
Brooks Products, Inc., No. 3-1/2T, Quikset W.17 Associated, or equal.
Mark cast iron cover, as per OWNER standards. Boxes shall be
inspected and approved by the Owner prior to site delivery.
G. Use special boxes where
indicated on the Drawings.
2.5 TERMINAL JUNCTION BOXES (TJB)
A. Provide hinged-cover terminal
junction boxes of the required type and size where
indicated. Utilize NEMA 12 enclosures for indoor dry locations.
Utilize NEMA 4X enclosures, as described under article 2.4,
JUNCTION AND PULL BOXES, for outdoor or wet locations or where
subscript WP is indicated at the box location on the Drawings.
Utilize NEMA 7, explosion proof enclosures for hazardous locations.
Provide terminal blocks with a separate connection point for each
conductor entering or leaving the box. Provide 25 percent spare
terminal points for future use following completion of
installation. Paint interior surfaces with white enamel or lacquer.
2.6 TELEPHONE TERMINAL CABINETS
A. Provide telephone terminal cabinets
of the type and size indicated for incoming telephone service.
Provide hinged doors code-gauge galvanized steel box containing a
3/4-inch plywood backboard. Utilize cabinet conforming to the
requirements of the Telephone Company. Provide terminal blocks with
25 percent spare termination points for future use following
completion of installation. Label and identify all conductors.
2.7 WIRING DEVICES A. Switches
1. General Use Switches: Provide
specification grade, totally-enclosed, ac type, quiet tumbler
switches meeting NEMA WD 1 performance standards and Federal
Specification W-S-896E, and capable of control of 100 percent
tungsten filament and fluorescent lamp loads. Use switches rated at
20 amps, 120/277 volts. Provide operating handles colored ivory in
office areas, and brown in all other areas. Switches shall have screw
terminals.
2. Weatherproof Switches: Use
switches mounted in a cast metal box with gasketed,
weatherproof device plate.
3. Switches with Pilot Lights:
Provide switches with 125-volt, neon light with red jewel, or lighted
toggle which is lighted when the switch is ON.
4.
Acceptable Manufacturers: Bryant, General Electric, Hubbell,
Pass and
Seymour, or equal. B.
Receptacles
1. Single and Duplex: Provide
specification grade receptacles meeting NEMA WD 1 performance
standards and Federal Specification W-C-596, and having a contact
arrangement such that contact is made on two sides of each inserted
blade without detent. Use two-pole, three-wire grounding type
receptacles rated 20 amps, 125 volts, NEMA Configuration 5-20R, and
with screw type wire terminals suitable for No. 10 AWG.
Provide high strength thermoplastic bases colored ivory in office
areas, and brown in all other areas. Acceptable manufacturers:
Bryant, General Electric, Hubbell, Pass and Seymour, Sierra, or
equal.
2. Weatherproof Receptacles:
Receptacles shall be specified above mounted in a cast metal box with
gasketed, weatherproof device plate as specified below.
3. Generator Receptacle: Generator
receptacles shall be 200 Amp, 480 V AC, 3 phase generator plug
compatible with Owner portable generator plugs. The generator
receptacle shall be Crouse-Hinds AP20458 Arktite Heavy Duty Circuit
Breaking Receptacle, or approved equal.
4. Ground Fault Interrupter (GFI)
Receptacles: Provide duplex specification grade GFI receptacles
tripping at 5 milliamps; rated 20 amps, 120 volts, NEMA Configuration
5-20R; and capable of interrupting 1,000 amps without damage. Use
units meeting NEMA WD 1, fitting standard sized outlet boxes, having
No.
12 AWG copper TW insulated pigtails,
having provision for testing, and ivory in color. Use standard
model where ground fault protection is needed at an individual
location. Use feed-thru model where ground fault protection
is
specified for "downstream"
conventional receptacles. Provide receptacles
accepting standard device plates.
Acceptable manufacturers: Pass and
Seymour, Square D, General Electric, or
equal.
5. Special Purpose Receptacles:
Provide receptacles of the type, rating, and number of poles
indicated or required for the anticipated purpose. Furnish a
matching plug with cord-grip features for each special purpose
receptacle.
6. Receptacles in Classified Areas:
Receptacles located in classified areas shall comply with the
requirements of NEC Article 500.
C. Multioutlet Surface Raceway System:
Provide Plugmold 2000, Walker Duct 2GW, or equal, with three-wire
grounding receptacles on indicated inch centers. Provide an
insulated grounding conductor to each receptacle. Wherever a
two-circuit, three-wire supply to a multioutlet system is indicated,
wire alternate outlets to each circuit and make receptacle color
alternate ivory black. Utilize gray raceway with ivory receptacles.
D. Telephone Outlets: Provide empty
outlet boxes and cover plates conforming to the requirements of the
telephone company where telephone outlets are indicated.
E.
Device Plates
1. General
a. Provide plates fitting closely and
tightly to the box on which they are to be installed. On surface
mounted boxes, provide plates, which do not extend beyond the sides
of the box unless the plates do not have sharp corners or edges.
b. Use plate material compatible with
the box material such that galvanic corrosion of the plate and/or box
does not occur.
2. Plastic (P) Plates:
Provide specification grade device plates manufactured of
0.10-inch minimum thickness,
noncombustible, thermosetting material. Provide ivory one-piece with
smooth exterior faces and with oval-head metal mounting screws of a
color matching that of the plate.
3. Metal (M) Plates: Provide
specification grade, one-piece, 0.040-inch nominal minimal thickness,
No. 430 satin finish 316 stainless steel device plates with
oval-head, matching mounting screws.
4. Engraved Plates: Where device
titles are indicated, provide device plates engraved with the
designated titles. Provide engraved letters, numbers, or characters
3/16 -inch high with filler of black color.
5. Cast Metal (CM) Plates: Provide
cast metal device plates of malleable ferrous metal or copper-free
aluminum with gaskets and 316 stainless steel screws with oval heads.
6. Weatherproof (WP) Plates
a. Where weatherproof receptacles are
designated, the receptacle shall be installed in the specified box
with a gasketed, weatherproof, cast metal or 316 stainless steel
cover plate with individual cap over each receptacle opening
and 316 stainless steel mounting screws. Utilize plates with caps
held tightly closed with 316 stainless steel springs when receptacle
is not in use. Acceptable manufacturers: General Electric,
Bryant, Hubbell, Sierra, Pass and Seymour, Crouse-Hinds, Bell,
or equal.
b. Where weatherproof switches are
designated, the switch shall be installed in the specified box
with a gasketed, weatherproof, cast metal cover plate incorporating
an external operator for the internal switch and with 316 stainless
steel mounting screws. Acceptable manufacturers and types:
Crouse-Hinds DS-181 or DS-185, Appleton FSK-1VTS or FSK-1VS, or
equal.
7. Raised Sheet Metal (SM) Plates:
Provide 1/2-inch high zinc or cadmium-plated steel device plates
designed for one-piece drawn type sheet steel boxes.
2.8
LIGHTING AND POWER DISTRIBUTION PANELBOARDS
A. General: Provide circuit breaker
panelboards including those in motor control center meeting
standards established by UL, NEMA PB 1, and the NEC. Where
used as service entrance equipment, provide panels UL labeled for
that use. Furnish panels with fully rated short circuit current
equipment rating. Series connected equipment ratings are not
acceptable. Provide panels rated for connection to an electric
system having an available amperes rms symmetrical short circuit
current of the indicated value at 120/240 volts. Provide panelboards
and circuit breakers suitable for use with 75 degrees C wire at full
NEC 75 degrees C ampacity.
B. Cabinets: Furnish boxes large
enough to provide a minimum wiring gutter space on both sides and top
and bottom of 4-inches by 4-inches minimum. Provide flush or
surface mounted boxes as indicated manufactured with reinforced steel
frame and code-gauge, hot-dip galvanized sheet steel. Utilize front
trim the same size as the box for surface mounted panelboards and
3/4-inch larger all around than the box for flush mounted
panelboards. Panel covers shall be installed with direct screw
connections. Adjustable clamps shall not be used. Utilize fronts
having doors with concealed hinges and flush type lock and catch
device. Provide multi-point locking devices for all doors over 30-
inches in height. Key all locks alike, and furnish two milled type
keys with each lock. Furnish on door interior a metal directory
frame with transparent plastic face and enclosed directory
card. Furnish an engraved, laminated plastic nameplate screwed (no
adhesives) to the cabinet exterior face indicating the panelboard
designation, service voltage, and phases. Nameplates shall be white,
engraved to a black core. Letter height shall be 1/4 inch.
C. Interiors
1. Furnished factory assembled
panelboard interiors complete with circuit breakers as shown. In
addition, space for future circuit breakers shall be provided with
easily removable front cover. Utilize panelboards with interiors
designed so that circuit breakers can be replaced without disturbing
adjacent circuit breakers or without removing the main bus.
2. Provide copper bus bars full
sized throughout their length. Make complete provisions for
mounting future circuit breakers throughout the full length of the
bus. Provide all machining, drilling, or tapping required to add or
change circuit breakers in the future. Bolt together and rigidly
support bus bars and connection straps on molded insulators.
3. Furnish an insulated neutral bus bar
rated the same as the phase bus bars and having at least one terminal
screw for each branch circuit. Furnish a copper ground bus bar
installed on the panelboard frame, bonded to the box, and
containing at least one terminal screw for each circuit. Provide
solderless main lugs for main, neutral, and ground bus bars. Provide
sub-feed or thru-feed lugs where indicated. Provide lugs and
connection points on phase, neutral, and ground buses suitable for
copper conductors.
D. Circuit Breakers
1. Furnish indicating type molded
circuit breakers providing ON/OFF and TRIPPED positions of the
operating handle. Furnish thermal magnetic, quick-make, quick- break
circuit breakers which are noninterchangeable in accordance
with the NEC. Do not use tandem or dual circuit breakers in normal
single-pole spaces.
Do not use
single-pole circuit breakers with handle ties where multiple circuit
breakers are indicated. Utilize multipole circuit breakers designed
so that an overload on one pole automatically causes all poles to
open. Provide circuit breakers meeting requirements of NEMA AB 1.
Install bolt-on circuit breakers in all panelboards. Provide
circuit breaker handle padlocking provisions where indicated or
required.
2. Where ground fault interrupter (GFI)
circuit breakers are indicated or required by the NEC, provide a unit
containing a conventional thermal magnetic trip and a ground fault
sensor rated to trip the circuit breaker in approximately 0.025
second for a 5-milliampere ground fault (UL Class A sensitivity).
Utilize a ground fault sensor having the same rating as the circuit
breaker and having a push-to-test button.
E. Acceptable Manufacturers:
Bryant, Cutler-Hammer, General Electric, Gould I-T-E, Square D,
Westinghouse, or equal.
2.9 CIRCUIT BREAKERS, INDIVIDUAL,
600 VOLTS AND LESS
A. Mount individual circuit breakers in
NEMA 12, industrial use enclosure unless otherwise indicated.
Provide NEMA 4X, 316 stainless steel raintight enclosures for circuit
breakers mounted outdoors and wherever the subscript WP is indicated
on the Drawings. Provide circuit breakers with handles that can be
locked in the OFF position. Interlock enclosure and circuit breaker
to prevent opening the cover with the circuit breaker in the ON
position. Provide quick-make, quick-break, thermal magnetic
circuit breakers of the indicating type showing ON/OFF and TRIPPED
positions of the operating handle. Do not use single-pole circuit
breakers with handle ties where multipole circuit breakers are
indicated. Utilize multipole circuit breakers designed so that an
overload on one pole automatically causes all poles to open.
Provide circuit breakers meeting the requirements of NEMA AB 1
and having a minimum interrupting rating as indicated. Where used
as service entrance equipment, provide units labeled for that use.
Provide circuit breakers suitable for use with 75 degrees C
wire at full NEC 75 degrees C ampacity.
2.10 FUSED SWITCHES, INDIVIDUAL, 600
VOLTS AND LESS
A. Mount individual fused switches in
NEMA 12, industrial use enclosures unless otherwise indicated.
Provide NEMA 4X, 316 stainless steel raintight enclosures for fused
switches mounted outdoors and wherever the subscript WP is indicated
on the Drawings. Provide fused switches that can be locked in the
OFF position. Interlock enclosure and switch to prevent opening the
cover with the switch in the ON position. Provide fused switches,
which are quick-make, quick-break, motor rated, load-break,
heavy-duty (HD) type having external marking clearly indicating ON
and OFF positions. Provide fuses of the current ratings indicated
and types specified herein. Utilize fuse mountings that reject Class
H fuses and will accept only the current-limiting fuses specified.
Provide fused switches meeting the requirements of NEMA KS 1 and UL
listed for application to a system having an available short circuit
current as indicated. Provide switches suitable for use with
75 degrees C wire at full NEC 75
degrees C ampacity.
2.11
NONFUSED SWITCHES, INDIVIDUAL, 600 VOLTS AND LESS
A. Mount individual switches in
NEMA 12, industrial use enclosure unless otherwise
indicated. Provide NEMA 4X, 316 stainless steel raintight
enclosure for switches mounted outdoors and wherever the subscript
WP is indicated on the Drawings. Provide switches that can be locked
in the OFF position. Interlock enclosure and switches to prevent
opening the cover with the switch in the ON position. Provide
switches, which are quick-make, quick-break, motor rated, load-break,
heavy-duty (HD) type having external marking clearly indicating ON
and OFF positions. Furnish switches meeting the requirements of NEMA
KS 1. Provide switches [with terminals] suitable for use with
75 degrees C wire at full NEC 75
degrees C ampacity.
2.12 FUSES, 600 VOLTS AND LESS
A. Provide a complete set of
current-limiting fuses wherever fuses are indicated. Provide listing
quantities each type and each current rating installed. Utilize
fuses that fit mountings specified with switches and which provide
features rejecting Class H fuses. Provide the following types:
1. For motor and transformer
circuits, 600 volts and less, 0 to 600 amps, UL Class
RK-1 with time delay, Bussmann Type
LPS-RK, Shawmut Type A6D-R, or equal.
2. For motor and transformer
circuits, 250 volts and less, 0 to 600 amps, UL Class
RK-1 with time delay, Bussmann Type
LPN-RK, Shawmut Type A2D-R, or equal.
3. For feeder and service
circuits, 600 volts and less, 0 to 600 amps, UL Class RK-
1, Bussmann Type KTS-R, Shawmut Type
A6K-R, or equal.
4. For feeder and service
circuits, 250 volts and less, 0 to 600 amps, UL Class RK-
1, Bussmann Type KTN-R, Shawmut Type
A2K-R, or equal.
5. For feeder and service
circuits, 600 volts and less, 601 to 6,000 amps, UL Class
L, Bussmann Type KRP-C, Shawmut Type
A4BY, or equal.
2.13 PUSHBUTTONS, INDICATING LIGHTS,
AND SELECTOR SWITCHES
A. For nonhazardous, indoor, dry
locations, including motor control centers, control panels, and
individual stations, provide heavy-duty, oil tight type pushbuttons,
indicating lights, selector switches, and stations for these devices.
Utilize General Electric Type CR 104P, or equivalent by Square D,
Cutler-Hammer, or other acceptable manufacturer.
B. For nonhazardous, outdoor, or
normally wet locations, or where otherwise indicated, provide
heavy-duty corrosion-resistant, watertight type pushbuttons,
indicating lights, or selector switches mounted in NEMA 4X 316
stainless steel watertight enclosures. Provide special gasketing
required to make complete station watertight. Utilize Square D Type
SK, or equivalent by General Electric, Cutler-Hammer, or other
manufacturers.
C. Provide devices meeting the
requirements of NEMA ICS 2, and having individual, extra large
nameplates indicating their specific function. Provide pushbutton
stations with laminated plastic nameplates indicating the drive they
control. Provide contacts with NEMA designation rating A600.
Install provisions for locking pushbuttons and selector switches in
the OFF position wherever lockout provisions are indicated.
D. For
hazardous locations, enclosures for push buttons, indicating
lights and selector switches shall be approved for classified areas
and shall be in compliance with NEC Article 500.
E. Utilize selector switches having
standard operating levers. Make all indicating lights push- to-test
type. Provide ON or START pushbuttons colored black. Provide OFF or
STOP pushbuttons colored red.
F. Control Stations. Pushbuttons,
selector switches and pilot lights shall be heavy duty, oil
tight/watertight devices installed in NEMA 4X enclosures, NEMA and
MCCs and control panels. These devices shall be as manufactured by
Allen-Bradley, Square D Company. General Electric or equal.
“START-LOCKOUT-STOP” pushbutton stations shall be Class
1 Division 1 installed adjacent to each
motor unless specifically indicated otherwise on the Contract
Documents.
G. Emergency stop pushbuttons shall
have a large, red mushroom head, maintained contacts,
push-to-stop, pull-to-rest, Allen-Bradley Bulletin 800T or equal.
H. Provide low voltage gold
plated contact blocks for all analog signals.
I. Indicating lights shall be 120V LED
lamps, push-to-test type, and shall be heavy-duty, oil tight (NEMA
13) for indoor enclosures and corrosion resistant, and water tight
(NEMA 4X) for outdoor enclosures with LED lamp. Each LED lamp shall
be nickel-plated with a screwed-on glass prismatic lens approximately
one-inch in diameter. Indicating lights shall be colored LED or
white LED with colored lens. Each light shall have a factory-
engraved nameplate, as shown on the Contract Drawings. Indicating
lights shall be General Electric Type CR104, Square D Class 9001 Type
SK and K, Allen-Bradley 800T and 800H series, or equal.
J. Provide 600-volts terminal blocks
for termination of all control circuits entering or leaving
equipment, panels, or boxes. Provide screw clamp compression, dead
front barrier type terminal blocks with current bar providing direct
contact with wire between the compression screw and yoke.
Provide yoke, current bar, and clamping screw constructed of
high strength and high conductivity metal. Utilize yoke that guides
all strands of wire into the terminal. Utilize current bar providing
dependable vibration-proof connection. Supply terminals constructed
to allow connection of wire without any special preparation other
than stripping. Rail mount individual terminals to create a
complete assembly and provide terminals constructed such that jumpers
can be installed with no loss of space on terminal or rail.
K. Size all terminal block components
to allow insertion of all necessary wire sizes and types. Supply
terminal blocks with marking system allowing the use of preprinted or
field- marked tags. Supply CSA certified and UL approved terminal
blocks manufactured by Weidmuller, Ideal, Electrovert, or equal.
Provide terminal blocks with 25 percent spare termination points for
OWNERS use following completion of installation.
2.14 CONTROL RELAYS
A. Provide magnetic control
relays, NEMA Class A600 (600 volts, 10 amps continuous,
7,200VA make, 720VA break), industrial
control type with field convertible contacts, and meeting the
requirements of NEMA ICS 2. Provide Cutler-Hammer Type M-600,
General Electric Type CR120B, or equal.
B. Where
time delay relays are specified or required, unless otherwise
noted, provide magnetic control relays with a timer attachment
adjustable over the range specified on the Drawings.
C. Where latching (mechanically held)
relays or motor thermal detector relays are specified, provide
magnetic control relays with mechanical latch attachment with
unlatching coil and coil clearing contacts. Utilize an
attachment allowing easy manual latching and unlatching.
D. Control relays shall be industrial
type, 600 V, with 10 A contacts and contact arrangement and
operating coils of the proper voltage rating as required by
the control circuit sequence and the Contract Documents.
Each relay shall have a minimum of four reversible-pole
contacts. The coils shall be sealed by pressure molding. The relays
shall be as manufactured by Allen-Bradley, Square D Company, General
Electric, or equal.
E. Intrinsically safe relays shall
allow the use of any type of remote pilot device located in Class 1
(hazardous) locations by providing a pilot circuit incapable of
releasing sufficient electrical energy to ignite gases or vapors
classified in Groups A, B, C and D. The units shall have an output
relay with double pole, double throw (DPDT) contacts rated at least
16 A at 120 VAC and 24 VDC, resistive
load. They shall operate on the AC supply voltage indicated on the
Contract Documents. The intrinsically safe relays shall be
Cutler-Hammer BW Series or equal.
F. Control relays for the level
signal shall have gold plated contacts as manufactured by
Allen Bradley, Phoenix Contact or
equal. Ice Cube Control Relays shall be industrial type,
120 VAC or 24 VDC, with 5 A
G. Ice Cube Control Relays shall be
industrial type, 120 VAC or 24 VDC, with 5 A contact arrangement and
operating coils of the proper voltage rating as required by the
control circuit sequence and the Contract Documents. Each relay
shall have a minimum of four reversible-pole contacts. The coils
shall be sealed by pressure molding. The relays shall be as
manufactured by Allen-Bradley 700HC, Square D Company, General
Electric, or equal.
2.15 RESET TIMERS
A. Timers that require pins or other
removable trip devices shall be provided with at least one pin or
trip device for each possible time setting.
1. Reset timers and repeat cycle timers
shall be heavy duty, industrial-type timers as manufactured by Eagle,
Paragon, or equal.
2. Twenty-four hour timers shall
be heavy duty, industrial-type timers as manufactured by
Paragon, Tork, or equal.
B. Timing relays shall be
Automatic Timing and Controls (ATC) Type 328A or equal.
2.16 ELECTRONIC TIMERS
A. Electronic timers shall be
provided where required.
2.17
MAGNETIC CONTACTORS
A. Provide contactors of the NEMA sizes
indicated. Mount contactors in NEMA 12, dust- tight, drip-tight,
industrial use enclosures unless otherwise indicated. Utilize
contactors manufactured and rated in accordance with NEMA ICS 2.
2.18 PENETRATION SEALING SYSTEMS
A. All penetration sealing
systems shall be per manufacturer’s requirements.
2.19 ENCLOSURE PAINT AND FINISH
A. All metallic enclosures shall be
finished with a prime coat of rust inhibitor and painted as per ANSI
No. 61 or as per the Engineer's instructions.
2.20 DRY TYPE SMALL POWER
TRANSFORMERS (600-VOLTS AND LESS PRIMARY)
A. Provide self-cooled, two-winding,
dry type transformers of the ratings indicated and built in
accordance with the latest IEEE, ANSI, and NEMA standards. Utilize
units with manufacturer's standard insulation class and standard
temperature rise. For ratings 3 to
25 kVA single-phase and 3 to 15 kVA
3-phase, provide units with core and coils completely
enclosed in a nonventilated, NEMA 12 enclosure. Utilize
encapsulated windings on single-phase units 0 to 25 kVA. On all
transformers 15 kVA and larger provide units with at least four,
2-1/2 percent, full capacity voltage taps; two above and two below
normal voltage rating.
B. Supply units where sound
levels determined by tests in accordance with NEMA and ANSI
standards do not exceed: 45 decibels.
C. Acceptable Manufacturers:
General Electric, Square D, Westinghouse, or equal.
2.21 LOW VOLTAGE SURGE PROTECTIVE
EQUIPMENT
A. Provide secondary surge protective
equipment consisting of a surge capacitor and surge arrestor
combination located where indicated on the Drawings. Utilize
components for all surge protective equipment covered by this
Specification, designed and tested in accordance with NEMA LA-1 and
ANSI/IEEE C62.1. Low voltage surge protection shall be obtained
from the Motor Control Center manufacturer.
2.22 ENCLOSURE PAINT AND FINISH
A. All metallic enclosures shall be
finished with a prime coat of rust inhibitor and painted as per
ANSI No. 61 or as per the Engineer's
instructions.
2.23 AUTOMATIC TRANSFER SWITCH
A. Provide 1200 amp and 600 amp, 3
pole, U.L. 1008 listed open transition automatic transfer switches
with close and withstand rating the same as the service meter panel
rating and not less than 65,000 RMS symmetrical amperes. Rating
shall be obtained without contact welding. The close and withstand
rating shall be verified by UL witnessed test on representative test
samples and shall be the rating in UL listing procedures for the
transfer switches supplied.
B. 600 volt
class, contactor type, over-center mechanism, double-throw
construction, positive electrically and mechanically interlocked to
prevent simultaneous closing, and mechanically held in both normal
and emergency positions. Transfer switch using interlocked circuit
breakers or molded case switches is not acceptable.
C. Automatic transfer switch
shall be capable of full load manual transfer in either direction.
Provide insulated manual operating
handle. The manual handle shall be permanently attached. Provide
means to verify that switch is not inadvertently left in manual
position.
D. Contacts shall be high-pressure,
silver alloy with separate arcing contacts. Arc chutes shall be made
of heat absorbing material and include metal leaves and arc chutes
insulating covers.
E. Neutral contact shall be of the same
design and have the same steady state, withstand and closing ratings
as phase contacts. Neutral and phase contacts shall be mounted on a
common crossbar arranged for simultaneous switching.
F. Provide fully rated copper lugs for
normal, emergency, load and neutral conductors inside cabinet.
Provide lugs to match the quantity and size of the installed
conductors. Power switching contacts and cable connections shall
have transparent protective covers for protection and visual
inspection. Provide copper lug for generator grounding.
G. Provide electronic controls,
front accessible, mounted inside the cabinet door. All
adjustable voltage sensors and time delays shall be solid state.
Provide control disconnect plugs to de-energize control circuits for
service and testing. Controls shall meet IEEE-587-1980 requirements
for surge withstand.
H. Utility voltage sensors
shall be close differential type that monitor each phase
individually.
Voltage averaging is not acceptable.
Monitors shall be temperature compensated; pick- up shall be
adjustable from 85% to 98% of nominal voltage, set at 90%; dropout
shall be adjustable from 75% to 98% of pick-up, set at 85%.
I. Generator voltage sensors shall
be close differential type that monitor each phase
individually; Frequency sensors shall monitor emergency source with
pick-up set at 95% of nominal frequency.
J. Operating power for transfer and
retransfer shall be obtained from the source to which the load is
being transferred. Maximum transfer time in either direction shall
be six (6) cycles, unless otherwise specified.
K. Provide the following time
delays and components:
1. Start delay 0 to 5 seconds
set at 2.
2. Transfer to emergency delay
set at 0.
3. Retransfer to normal delay 0
to 30 minutes set at 10.
4. Retransfer delay bypass, key
operated.
5. Unloaded running delay, 0 to
10 minutes set at 5.
6. Delay transition, both
directions, isolating load from both sources, 0.5 -
7.5 seconds, set at 1 second.
7.
Test switch, key operated with and without transfer.
8. Four pilot lights on door
showing ATS position and source available.
9. Engine start contacts wired
to terminal block.
10. Contacts indicating ”normal
power on” wired to terminal block.
11. Contacts indicating “normal
power fail” wired to terminal block.
12. Contacts indicating
“generator running” wired to terminal block.
13. Electronic exerciser 7 day,
load/no load transfer.
L. Controls shall automatically
retransfer the load from emergency source to normal source if
emergency source fails and normal source is available.
M. Transfer switch shall be ASCO
4000 series, Zenith ZTS, or equal.
PART 3 - EXECUTION
3.1 OUTLET AND DEVICE BOXES
A. Installation
1. Mount boxes at the following heights
unless otherwise required by the Americans with Disabilities Act
(heights are to the centerline of the box):
a. Wall Switches: 48-inches
above floor b. Thermostats: 48-inches above floor
c. Wall Telephone Outlets:
48-inches above floor
d. Wall Mounted Telephone: 52-inches
above floor outlets for public pay telephone, 52-inches above floor
for standard wall telephone
e. Office, Lab Receptacles: Flush
device plate bottom or side with top of the splashback on use areas,
halls, etc. or 6-inches above counter tops without splashback;
12-inches above floor unless otherwise indicated.
2. Where above heights do not suit the
building construction or finish, locate boxes where directed by the
Engineer.
3. Locations indicated are
approximate.
a. Mount All Boxes Plumb and
Level: Use flush mounted boxes with concealed conduits. Make
edges of boxes flush with finished surface. Provide proper type
extension rings or plaster covers for this purpose. For flush mounted
boxes, make holes in the surrounding surface no larger than required
to receive the box.
b. Install
boxes in a secure, substantial manner supported independently of
conduit by attachment to the building structure or a structural
member. Fasten boxes with bolts and expansion shields on concrete or
brick, toggle bolts on hollow masonry units, and machine screws or
welded, threaded studs on steelwork. No power actuated tools are
permissible. Threaded studs driven in by a powder charge and provided
with lock washers and nuts are acceptable in lieu of expansion
shields. Boxes embedded in concrete or masonry need not be
additionally supported. Utilize galvanized mounting hardware in
industrial areas.
4. Open no more knockouts in sheet
steel boxes than are actually required. Seal any used openings in
any type box.
3.2 JUNCTION AND PULL BOXES
A. Where indicated on the Drawings, and
where necessary to terminate, tap-off, or redirect multiple conduit
runs, provide and install appropriately designed junction boxes.
Furnish and install pull boxes where necessary in the raceway system
to facilitate conductor installation. Provide pull boxes to limit
conduit runs to less than 150-feet and to contain no more than the
equivalent of three right-angle bends unless accepted by the
Engineer.
1. Types to be provided:
a. Use boxes of the types listed for
specific locations under article 2.3, OUTLET AND DEVICE BOXES.
b. Use outlet boxes as junction boxes
and pull boxes wherever possible and allowed by applicable codes.
c. Provide boxes as indicated for
below grade conduit. Provide 316 stainless steel (NEMA 4X) or
watertight, nonmetallic boxes as indicated for above grade locations.
2. Installation
a. Make All Boxes Accessible: Do not
install boxes in finished areas unless accepted by the Engineer.
Mount all boxes plumb and level. Use flush mounted boxes with
concealed conduits. Make edges of recessed boxes flush with
the final surface.
b. Mount boxes in a secure, substantial
manner, supported independently of conduit by attachment to the
building structure or a structural member. Fasten boxes with bolts
and expansion shields on concrete or brick, toggle bolts on hollow
masonry units, and machine screws or welded threaded studs on
steelwork. Threaded studs provided with lock washers and nuts
as provided with Redhead or Hilti Kwik-bolt concrete anchors, Hilti
HIT adhesive anchors may be used for bolt sizes 3/8" and smaller
are acceptable in lieu of expansion shields. Boxes embedded in
concrete or masonry need not be additionally supported. No Powder-
charged tools are allowed. Utilize 316 stainless steel mounting
hardware in industrial areas.
c. Install boxes for conduits under
grade flush with finished grade in locations outside of paved
areas, roadways, or walkways.
d. If
adjacent structure is available, the box may be mounted on
the structure surface just above finished grade in accessible but
unobtrusive location. If it is found desirable to locate
boxes in paved areas, roadways, or walkways, obtain Engineer's
written approval and utilize boxes and covers suitable for the
weights to which they may be subjected.
3.3 TERMINAL JUNCTION BOXES (TJB)
A. Install in accordance with all the
requirements detailed under article 3.2, JUNCTION AND PULL BOXES
above. Label each block and terminal with a permanently attached,
nondestructible tag.
3.4 WIRING DEVICES
A. Switches: Mount switches at the
heights indicated under article 3.1, OUTLET AND DEVICE BOXES. Mount
switches for switch operation in the vertical position.
B. Receptacles: Mount receptacles at
heights indicated under article 3.1, OUTLET AND DEVICE BOXES. Mount
receptacles with grounding slot up Ground receptacles to boxes with
grounding wire, not by yoke or screw contact. Mount weatherproof
receptacles with the hinge for the protective cover above (not at
side, or below) the receptacle opening.
C. Telephone Outlets: Mount outlets
at the heights indicated under article 3.1, OUTLET AND DEVICE BOXES.
Mount outlets in the vertical position unless otherwise indicated.
END OF SECTION
No comments:
Post a Comment