Friday, January 23, 2015

SECTION 11317B DETAILED PUMP SPECIFICATION DENITRIFIED RAS PUMPS

This spec was part of the Des Plaines, IL River WRF project tat bid Feb 26, 2015.


SECTION 11317B

DETAILED PUMP SPECIFICATION DENITRIFIED RAS PUMPS


PART 1 GENERAL

1.1 SECTION INCLUDES

A. Denitrified RAS Pumps:
1. Denitrified RAS Pump No. 1: P-3-8-5.
2. Denitrified RAS Pump No. 2: P-3-8-6.

1.2 SYSTEM DESCRIPTION

A. The pumps will be used to transfer denitrified return activated sludge from RAS Denitrification Tank to the Aeration Tank influent splitter.

1.3 DESIGN REQUIREMENTS

A. General Requirements:
1. Tank Dimensions:
a. Length, ft: 37.75.
b. Width, ft: 40.
c. Sidewater Depth, ft: 16.
2. Liquid Pumped: Return Activated Sludge.
3. Specific Gravity: 1.0.
4. Maximum liquid temperature: 80° F.
5. Solids Content: 0.5 to 1.25%.
6. Pump orientation: Horizontal.
7. Motor Size: 4 HP.

B. Hydraulic Requirements:
1. Maximum Design Flow:
a. Flow, gpm: 3,100.
b. TDH, feet: 2.0
2. Minimum Design Flow:
a. Flow, gpm: 2,800.
b. TDH, feet: 1.8

1.4 SUBMITTALS

A. See General Pump Specification Section 11317, SUBMERSIBLE DIRECT DRIVE AXIAL FLOW PUMPS - GENERAL

1.5 DELIVERY, STORAGE AND HANDLING

A. See General Pump Specification Section 11317, SUBMERSIBLE DIRECT DRIVE AXIAL FLOW PUMPS - GENERAL

PART 2 PRODUCTS

2.1 See General Pump Specification Section 11317, SUBMERSIBLE DIRECT DRIVE AXIAL FLOW PUMPS – GENERAL.


PART 3 EXECUTION

3.1 See General Pump Specification Section 11317, SUBMERSIBLE DIRECT DRIVE AXIAL FLOW PUMPS - GENERAL




END OF SECTION