SECTION 11317B
DETAILED PUMP SPECIFICATION DENITRIFIED RAS PUMPS
PART 1 GENERAL
1.1 SECTION INCLUDES
A. Denitrified RAS Pumps:
1. Denitrified RAS Pump No. 1: P-3-8-5.
2. Denitrified RAS Pump No. 2: P-3-8-6.
1.2 SYSTEM DESCRIPTION
A. The pumps will be used to transfer denitrified return activated sludge from RAS Denitrification Tank to the Aeration Tank influent splitter.
1.3 DESIGN REQUIREMENTS
A. General Requirements:
1. Tank Dimensions:
a. Length, ft: 37.75.
b. Width, ft: 40.
c. Sidewater Depth, ft: 16.
2. Liquid Pumped: Return Activated Sludge.
3. Specific Gravity: 1.0.
4. Maximum liquid temperature: 80° F.
5. Solids Content: 0.5 to 1.25%.
6. Pump orientation: Horizontal.
7. Motor Size: 4 HP.
B. Hydraulic Requirements:
1. Maximum Design Flow:
a. Flow, gpm: 3,100.
b. TDH, feet: 2.0
2. Minimum Design Flow:
a. Flow, gpm: 2,800.
b. TDH, feet: 1.8
1.4 SUBMITTALS
A. See General Pump Specification Section 11317, SUBMERSIBLE DIRECT DRIVE AXIAL FLOW PUMPS - GENERAL
1.5 DELIVERY, STORAGE AND HANDLING
A. See General Pump Specification Section 11317, SUBMERSIBLE DIRECT DRIVE AXIAL FLOW PUMPS - GENERAL
PART 2 PRODUCTS
2.1 See General Pump Specification Section 11317, SUBMERSIBLE DIRECT DRIVE AXIAL FLOW PUMPS – GENERAL.
PART 3 EXECUTION
3.1 See General Pump Specification Section 11317, SUBMERSIBLE DIRECT DRIVE AXIAL FLOW PUMPS - GENERAL
END OF SECTION
No comments: